Corrigo ventilation 3.4 manu

Manual Corrigo Ventilation, revision R Chapter 15 Settings 77
Shutdown mode
Shutdown mode
P-band: 100.0 °C
I-time: 100 s
Frost protection temperature
Frost protection
Frost protection
Active
Setp shutdown: 25°C
P-band active: 5°C
Fast stop at frost-
protection alarm
Yes
"Setp shutdown" is the shutdown mode setpoint.
P-band active 5°C means that the frost protection controller will start overriding the heating output
when the frost protection temperature is less than five degrees above the set frost alarm limit. The
default alarm limit is 7°C. It can be changed in the menu Settings/Alarm settings/Alarm
limits/Alarm limit frost protection.
Exchanger de-icing
Deicing
P-band: 100 °C
I-time: 100 s
15.2 Control pressure
Pressure control SAF
Pressure control SAF
P-band: 500 Pa
I-time: 60 s
Min.output: 0 %
Pressure control EAF
Pressure contr EAF
P-band: 500 Pa
I-time: 60 s
Min.output: 0 %
15.3 Control flow
Flow control SAF
Flow control SAF
P-band: 1000 m3/h
I-time: 60 s
Min.output: 0 %