CORRIGO VENTILATION 3.X USER GUIDE
Table Of Contents
- About this user guide
- About Corrigo
- Display, buttons and LEDs
- The menu system
- Navigating the menus
- Running mode
- Temperature
- Setpoint Supply air temperature control
- Setpoint Outdoor temperature compensated Supply air control
- Setpoint Cascaded room temperature control
- Setpoint Cascaded extract air temperature control
- Setpoint Outdoor compensated room temperature/extract air control
- Support control heating/Support control cooling
- Frost protection temperature
- Exchanger de-icing
- Heat exchanger efficiency monitoring
- Recirculation
- Extra controller unit
- Enthalpy control
- Air control
- Pressure control SAF (there are also corresponding menus for EAF)
- Flow control SAF (there are also corresponding menus for EAF)
- Manual frequency control SAF (there are also corresponding menus for EAF)
- Frequency control external
- Frequency control SAF with EAF slave/flow control (also available for opposite function)
- CO2
- Humidity control
- Time settings
- Access rights
- Other functions
- Index
The menu system Corrigo ventilation user guide, revision F
12
Setpoint Cascaded room temperature control
In control mode Supply air control/Room control, the
setpoint is used when cascade connected room control is
active.
Submenu for setting the min and max limitation
temperatures for the supply air.
If two room sensors have been configured you
will also get this menu. The controller uses the
average temperature of the two sensors.
Setpoint Cascaded extract air temperature control
In control mode Supply air control/Extract air control,
the setpoint is used when cascaded extract air control is
active.
Sub menu for setting the min and max limitation
temperatures for the supply air.
Setpoint Outdoor compensated room temperature/extract air control
Offers the possibility to compensate the room
temperature/extract air temperature against the outdoor
temperature. Note that the curve must be adjusted for
optimal functionality!
Room temp1
Actual: 22.0°C
Setpoint: 21.5°C
If cascade control
max/min supply setp
Max: 30.0°C
Min: 12.0°C
Room temp2
Actual: 21.8°C
Extract air temp
Actual: 21.0°C
Setpoint: 21.1°C
If cascade control
max/min supply setp
Max: 30.0°C
Min: 12.0°C
Room temp1
Actual: 22.0°C
Setp: 21.5°C