CORRIGO VENTILATION 3.X USER GUIDE
Table Of Contents
- About this user guide
- About Corrigo
- Display, buttons and LEDs
- The menu system
- Navigating the menus
- Running mode
- Temperature
- Setpoint Supply air temperature control
- Setpoint Outdoor temperature compensated Supply air control
- Setpoint Cascaded room temperature control
- Setpoint Cascaded extract air temperature control
- Setpoint Outdoor compensated room temperature/extract air control
- Support control heating/Support control cooling
- Frost protection temperature
- Exchanger de-icing
- Heat exchanger efficiency monitoring
- Recirculation
- Extra controller unit
- Enthalpy control
- Air control
- Pressure control SAF (there are also corresponding menus for EAF)
- Flow control SAF (there are also corresponding menus for EAF)
- Manual frequency control SAF (there are also corresponding menus for EAF)
- Frequency control external
- Frequency control SAF with EAF slave/flow control (also available for opposite function)
- CO2
- Humidity control
- Time settings
- Access rights
- Other functions
- Index
Corrigo ventilation user guide, revision F The menu system
13
This function operates according to the assumption that
one may accept a slightly higher indoor temperature
when it is warm outside and vice versa, providing an
excellent opportunity for conserving energy.
Support control heating/Support control cooling
Support control is normally used when room temperature
control or extract air control has been configured, to
prevent a too large offset in temperature when the unit is
“Off”.
“Support control Heating” or “Support control Cooling”
will run if support control is configured, the running
mode is "Off" (timer control OFF and not in extended
running) and if conditions call for support control.
Minimum run time is settable 0 to 720 minutes (FS= 20 minutes).
Frost protection temperature
Relevant value for the water temperature at the frost
protection sensor. Frost protection can be set to function
either on Y1, Y4 or on both. The function only supports
a single sensor.
Outdoor comp setp
-20.0°C = 25.0°C
-15.0°C = 24.0°C
-10.0°C = 23.0°C
Outdoor comp setp
-5.0°C = 23.0°C
0.0°C = 22.0°C
5.0°C = 20.0°C
Outdoor comp setp
10.0°C = 19.0°C
20.0°C = 18.0°C
If cascade control
max/min supply setp
Max: 30.0°C
Min: 12.0°C
Support heating
Room temp for
Start: 15.0°C
Stop: 21.0°C
Support cooling
Room temp for
Start: 30.0°C
Stop: 28.0°C
Frost protection
Actual: 30.9°C