CORRIGO VENTILATION 3.X USER GUIDE

Table Of Contents
The menu system Corrigo ventilation user guide, revision F
16
Air control
This menu is only shown if frequency controlled fans have been configured.
Depending on the choice of fan control, different combinations of the menus below will be
shown.
Pressure control SAF (there are also corresponding menus for EAF)
Here, Actual and Setpoint values are displayed. This is a
read-only menu. No settings can be made here.
Submenu Setpoint values for normal speed (1/1)
and reduced speed (1/2).
Submenu outdoor compensation. An outdoor
temperature dependent compensation of the
pressure setpoint value can be added. The
compensation can be set for either the supply air
fan alone or for both fans.
Submenu extra compensation. A
temperature dependent compensation
similar to the one above but with
selectable temperature source.
Flow control SAF (there are also corresponding menus for EAF)
Setpoint Flow control. Here, Actual and Setpoint values
are displayed. This is a read-only menu. No settings can
be made here.
Submenu Setpoint values for normal speed (1/1)
and reduced speed (1/2).
Submenu Outdoor compensation. An outdoor
temperature dependent compensation of the
pressure setpoint value can be added. The
compensation can be set for either the supply air
fan alone or for both fans.
Pressure control SAF
Actual: 480 Pa
Setp: 490 Pa
Setp 1/1: 490 Pa
Setp 1/2: 300 Pa
-20 °C = -50 Pa
10 °C = 0 Pa
Comp sens:Room temp1
15 °C = 0 Pa
20 °C = 0 Pa
25 °C = 0 Pa
Flow control SAF
Actual: 1800 m3/h
Setp: 2000 m3/h
Setp 1/1: 2000 m3/h
Setp 1/2: 1000 m3/h
-15 °C =-200.0 m3/h
10 °C = 0.0 m3/h