400895 Topvex FR Operation and Maintenance Instructions

Topvex FR800, FR1600, FR3800 Operation and Maintenance Instructions
Systemair Inc.
19
Main menu item Sub-menu item 1 Sub-menu item 2 Explanations
→ C02/VOC
Control
C02/VOC active
Never
Type: Fan
Min. time: 60
min
In applications with varying
occupancy the fan speeds can
becontrolledbytheairquality
asmeasuredbyC02/VOC-
sensor. See encl. corrigo manual
(CD) for det. explanation
Set active to Never, Always
or If time channel off.
Set what should be regulated.
Select type Fan
Set the min. time the unit is
activatedbytheC02/VOC
demand function
Activation
level
1/2-speed: 800
ppm
1/2-speed:
1000 ppm
diff: 160 ppm
Set the activation level as 1/2
speed
Set the activation level as 1/1
speed
Set allowed diff. value
→ Humidity
control
Humidity
control
Not active
Start limit:
15%
Stop limit: 5%
Set the humidity control to
Humid/Dehumidication,
Dehumidication,
Humidication or Not
active.
Set the start limit and stop limit
in %RH
Applicable for external
Humidicationor
Dehumidicationdevice.
→ Exchanger
frost prevention
Mode:
Off
Type:
Recirculation
Continue
exhausting
during
recirculation:
NO
Set mode to ON or OFF
Set Type to Recirculation or
Exhaust Only
Set exhaust air fan and exhaust
air damper operation for
recirculation to Yes or No.
→ Cooling
recovery
Cooling
recovery
No
Cooling limit:
35.6°F
Set the cooling recovery to Yes
or No.
Set the cooling limit (the
difference in temperature
between extract air and outdoor
air that activates the cooling
recovery).
→ Access rights → Log on Log on
Enter password
xxxx
Actual level:
None
Log on to service level by
entering a 4-digit code. After
reaching the desired level go
backwith“LEFT”arrow(press2
times) on the control panel.
Standard code from factory to
enter service level is 2222. Back
to operator level: 3333