CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU

16 Chapter 4 Input Register
Signal name
EXOL type
Modbus address
Default value
Function
Description
VentSettings.Cor_UAi3
X
3040
Universal inputs
Connected signal on UAI3: (See
signal list for UAI1)
VentSettings.Cor_UAi4
X
30041
Universal inputs
Connected signal on UAI4: (See
signal list for UAI1)
VentSettings.Cor_Di1(0)
X
30042
Digital inputs
Connected signal on DI1:
0=Not used
1=SAF-Ind
2=EAF-Ind
3=P1-Heating
4=P1-Exchanger
5=P1-Cooling
6=Filter guard
7=Fire alarm
8=Fire damper-ind
9=Ext run 1/1
10=Ext run ½
11=External alarm
12=External switch
13=Flow guard
14=Rot.sent.exch
15=De-icing
16=Frostprotection
17=Overheatprotection
18=Recirculation run
19=Change over
20=Filter guard 2
VentSettings.Cor_Di2
X
30043
Digital inputs
Connected signal on DI2: (See signal
list for DI1)
VentSettings.Cor_Di3
X
30044
Digital inputs
Connected signal on DI3: (See signal
list for DI1)
VentSettings.Cor_Di4
X
30045
Digital inputs
Connected signal on DI4: (See signal
list for DI1)
VentSettings.Cor_Di5
X
30046
Digital inputs
Connected signal on DI5: (See signal
list for DI1)
VentSettings.Cor_Di6
X
30047
Digital inputs
Connected signal on DI6: (See signal
list for DI1)
VentSettings.Cor_Di7
X
30048
Digital inputs
Connected signal on DI7: (See signal
list for DI1)
VentSettings.Cor_Di8
X
30049
Digital inputs
Connected signal on DI8: (See signal
list for DI1)