CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU

48 Chapter 5 Holding Register
Signal name
EXOL type
Modbus address
Default value
Function
Description
VentSettings.Cor_Supply
PID_Select
X
40369
2
Manual/Auto
Supply temp controller mode:
0=Manual off
1=Manual on
2=Auto
VentSettings.Cor_Supply
PID_ManSet
R
40370
0 %
Manual/Auto
Supply temp controller output if
manual on mode
VentSettings.Cor_SAFAu
toMode(0)
X
40371
3
Manual/Auto
Running mode SAF:
0=Off
1=Manual half speed
2=Manual full speed
3=Auto
VentSettings.Cor_EAFA
utoMode
X
40372
3
Manual/Auto
Running mode EAF:
0=Off
1=Manual half speed
2=Manual full speed
3=Auto
VentSettings.Cor_SAFFr
equenceAutoMode
X
40373
3
Manual/Auto
Running mode frequence controlled
SAF
0=Manual
1=Man. half speed
2=Man. Fullspeed
3=Auto
VentSettings.Cor_SAFM
anual
R
40374
0 %
Manual/Auto
Freguencer controller output SAF if
manual mode
VentSettings.Cor_EAFFr
equenceAutoMode
X
40375
3
Manual/Auto
Running mode frequence
controlled EAF
0=Manual
1=Man. half speed
2=Man. Fullspeed
3=Auto
VentSettings.Cor_EAFM
anual
R
40376
0 %
Manual/Auto
Freguencer controller output EAF if
manual mode
VentSettings.Cor_HeatCo
ilAutoMode(0)
X
40377
2
Manual/Auto
Running mode Heating:
0=Off
1=Manual
2=Auto
VentSettings.Cor_HeatCo
ilManual(0)
R
40378
0
Manual/Auto
Heating controller output if manual
mode
VentSettings.Cor_ExchC
oilAutoMode
X
40379
2
Manual/Auto
Running mode Exchanger:
0=Off
1=Manual
2=Auto
VentSettings.Cor_ExchC
oilManual
R
40380
0
Manual/Auto
Exchanger controller output if manual
mode
VentSettings.Cor_CoolC
oilAutoMode
X
40381
2
Manual/Auto
Running mode Cooling:
0=Off
1=Manual
2=Auto