CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU

52 Chapter 5 Holding Register
Signal name
EXOL type
Modbus address
Default value
Function
Description
VentSettings.Cor_Comp2
Pressure
R
40416
0
SAF/EAF Pressure
and Flow
Pressure compensation at breakpoint 2
VentSettings.Cor_Comp2
Temp
R
40417
10
SAF/EAF Pressure
and Flow
Outdoor temp breakpoint 2 (must be
higher than breakpoint 1 temp)
VentSettings.Cor_Humidi
tyMaxDiff
R
40418
10 % RH
Humidity
Max allowed difference between
setpoint and humidity in room before
alarm
VentSettings.Cor_Humidi
tyStartLimit
R
40419
15 % RH
Humidity
Start limit in % to start digital output
signal "Cor_HumidityStart(0)"
VentSettings.Cor_Humidi
tyStopLimit
R
40420
5 % RH
Humidity
Stop limit in % to stop digital output
signal "Cor_HumidityStart(0)"
VentSettings.Cor_Humidi
tyAutoMode
X
40421
2
Manual/Auto
Running mode humidity start signal
0=Off
1=On
2=Auto
VentSettings.Cor_ExchSt
artDelay
I
40422
0 s
Settings, General
Start delay Exchanger (s)
VentSettings.Cor_DXBlo
ckLimit
R
40423
0°C
Settings, General
If lower outdoor temperature all steps
for DX-cooling is blocked
VentSettings.Cor_SAFFu
llspeedOutput
R
40424
75 %
SAF/EAF Pressure
and Flow
Output signal (0...100 %) full speed
SAF if Frequency control manually
VentSettings.Cor_SAFHa
lfspeedOutput
R
40425
50 %
SAF/EAF Pressure
and Flow
Output signal (0...100 %) half speed
SAF if Frequency control manually
VentSettings.Cor_EAFFu
llspeedOutput
R
40426
75 %
SAF/EAF Pressure
and Flow
Output signal (0...100 %) full speed
EAF if Frequency control manually
VentSettings.Cor_EAFHa
lfspeedOutput
R
40427
50 %
SAF/EAF Pressure
and Flow
Output signal (0...100 %) half speed
EAF if Frequency control manually
VentSettings.Cor_CoolSt
epBlock1
R
40428
0 %
Settings, General
If frequens output signal SAF is lower
cool step 1 is blocked
VentSettings.Cor_CoolSt
epBlock2
R
40429
0 %
Settings, General
If frequens output signal SAF is lower
cool step 2 is blocked
VentSettings.Cor_CoolSt
epBlock3
R
40430
0 %
Settings, General
If frequens output signal SAF is lower
cool step 3 is blocked
VentSettings.Cor_CoolSt
epBlockLimit1(0)
R
40431
13°C
Settings, General
If lower outdoor temperature
Cool step 1 is blocked
VentSettings.Cor_CoolSt
epBlockLimit2
R
40432
13°C
Settings, General
If lower outdoor temperature
Cool step 2 is blocked
VentSettings.Cor_CoolSt
epBlockLimit3
R
40433
13°C
Settings, General
If lower outdoor temperature
Cool step 3 is blocked
VentSettings.Cor_ExtraU
nitFunc
X
40434
0
Extra Unit
Start/Stop function Extra Unit:
0=Off
1=Always running
2=Running if unit is running