CORRIGO VENTILATION 3.X USER GUIDE

Table Of Contents
The menu system Corrigo ventilation user guide, revision F
18
Frequency control SAF with EAF slave/flow control (also available for
opposite function)
A pressure control where either the SAF or EAF is
operated as a slave. This function is also available
featuring flow control.
Controller output
comp if cooling
0 at R U S= 0 %
100 at R U S= 0 %
Controller output
comp if heating
0 at R U S= 0 %
100 at R U S= 0 %
Controller output
compensation
Not active
Compensation only
when
1/1-speed : No
defrosting: No
Pressure ctrl SAF
Actual: 480 Pa
Setp.: 490 Pa
Pressure ctrl SAF
Setp 1/1: 500 Pa
Setp 1/2: 250 Pa
Outdoor comp output
-20 °C = 0 Pa
10 °C = 0 Pa
Act comp: 0 Pa
Comp sens:Roomtp.1 15
°C = 0 Pa
20 °C = 0 Pa
25 °C = 0 Pa