Corrigo ventilation Communication Guide 3.3 manu

12 Commonly used signals Communication guide
Signal name
EXOL type
Modbus address
BACnet
Default value
Function Description
VentActual.Cor_Ru
nMode
X 3 MSV,
40003
Actual/Setpoint Modbus:
0=Stopped
1=Starting up
2=Starting reduced
speed
3=Starting full speed
4=Starting normal run
5=Normal run
6=Support control
heating
7=Support control
cooling
8=CO2 run
9=Night cooling
10=Full speed stop
11=Stopping fan
BACnet:
1=Stopped
2=Starting up
3=Starting reduced
speed
4=Starting full speed
5=Starting normal run
6=Normal run
7=Support control
heating
8=Support control
cooling
9=CO2 run
10=Night cooling
11=Full speed stop
12=Stopping fan
VentActual.Cor_Su
pplyAirTemp
R 7 AV,
40007
Supply, Extract
and Room
temperatures
Supply air temperature
VentActual.Cor_Ex
tractAirTemp
R 9 AV,
40009
Supply, Extract
and Room
temperatures
Extract air temp
VentActual.Cor_Ro
omTemp1
R 10 AV,
40010
Supply, Extract
and Room
temperatures
Room temperature 1
VentActual.Cor_Ro
omTemp2
R 11 AV,
40011
Supply, Extract
and Room
temperatures
Room temperature 2
VentActual.Cor_S
AFPressure
R 13 AV,
40013
SAF/EAF
Pressure and Flow
Supply air fan pressure
(Pa)
VentActual.Cor_E
AFPressure
R 14 AV,
40014
SAF/EAF
Pressure and Flow
Extract air fan pressure
(Pa)
VentActual.Cor_S
AFAirFlow
R 15 AV,
40015
SAF/EAF
Pressure and Flow
Supply air fan flow
(m3/h). Scale factor = 1
VentActual.Cor_E
AFAirFlow
R 16 AV,
40016
SAF/EAF
Pressure and Flow
Extract air fan flow
(m3/h). Scale factor = 1