Corrigo ventilation Communication Guide 3.3 manu

Communication guide Appendix Alarm list 15
No. Alarm text Prio Description
39 Manual Extract Air Fan mode C Extract air fan in manual control
40 Freq. EAF Manual C Signal to SAF frequency converter in manual control
41 Heating Manual Manual C Heating output in manual control
42
Manual exchanger control
C
Heat exchanger output in manual control
43
Manual cooler control
C
Cooling output in manual control
44 Manual P1-Heater C Heating circulation pump in manual control
45 Manual P1-Exchanger C Exchanger circulation pump in manual control
46 Manual P1-Cooler C Cooling circulation pump in manual control
47 Fire damp. Manual C Fire dampers in manual control
48
Internal battery error
A
Internal battery needs replacing
49
Sensor error Supply Air temp
B
Malfunction of connected sensor
50
Sensor error Extract Air temp
B
Malfunction of connected sensor
51 Sensor error Room temp 1 B Malfunction of connected sensor
52 Sensor error Room temp 2 B Malfunction of connected sensor
53 Sensor error Exhaust air temp B Malfunction of connected sensor
54 Sensor error Extra sensor B Malfunction of connected sensor
55
Sensor error SAF pressure
B
Malfunction of connected sensor
56
Sensor error EAF pressure
B
Malfunction of connected sensor
57 Sensor error Deicing temp B Malfunction of connected sensor
58 Sensor error Frost Protection temp B Malfunction of connected sensor
59 Sensor error CO2 B Malfunction of connected sensor
60 Sensor error Humidity Room B Malfunction of connected sensor
61 Sensor error Humidity Duct B Malfunction of connected sensor
62
Sensor error Extra unit temp
B
Malfunction of connected sensor
63
Sensor error External control SAF
B
Malfunction of connected sensor
64 Sensor error External control EAF B Malfunction of connected sensor
65 Sensor error SAF Pressure 2 B Malfunction of connected sensor
66 Sensor error Humidity outdoor B Malfunction of connected sensor
77 Alarm Frequency converter SAF A Malfunction of frequency converter SAF
78
Alarm Frequency converter EAF
A
Malfunction of frequency converter EAF
79
Communication error Frequency SAF
C
Communication problem with Vacon NXL
80
Communication error Frequency EAF
C
Communication problem with Vacon NXL
81 Communication error Expansion unit 1 C Communication problem with a controller connected to port 2
82 Communication error Expansion unit 2 C Communication problem with a controller connected to port 2
83 Warning Frequency converter SAF C
84 Warning Frequency converter EAF C
85
Output in manual mode
C
Analogue or digital output in manual mode
86
Time for service
C
Time for service
87
Manual Y4-Extra Sequence control
C
Y4-Extra sequence in manual control
88 Restart blocked after power failure C Restart blocked after power failure
89 Manual Y5-Extra Sequence control C Y5-Extra sequence in manual control
90 Filter guard 2 B Filter guard pressure switch activated
91 High temp Extra sensor 1 - High temperature Extra sensor 1
92
Low temp Extra sensor 1
-