Manual Corrigo Ventilation, revision R Chapter 4 Commissioning 25
Chapter 4 Commissioning
General
Before the Corrigo can be used, all inputs and outputs must first be configured, as well as all
relevant parameters.
All commissioning can be done using the Corrigo front panel display and buttons or using the
external display unit E3-DSP.
E tool
©
The best way however, is to configure the Corrigo by using E tool
©
.
E tool
©
is a PC-based configuration program specially developed to simplify the commissioning of
the Corrigo series.
When using E tool
©
the whole configuration and all settings can be done on the computer and then
be downloaded to the Corrigo. An infinite number of different configurations can be saved in
computer memory for later use.
A communication cable is required in order to configure Corrigo. E-CABLE2-USB or E-CABLE-
RS232 are used for controllers featuring RS485 communication, and an E-CABLE-TCP/IP
crossover network cable for controllers with a TCP/IP port.
The Corrigo must be powered up and the application selected in order for it to be configured.
4.1 How to do it
For configuration using E tool
©
, see the E tool
©
manual.
For configuration using the front panel or E3-DSP, there are two ways to go depending on how
much help you need.
Option 1:
Jump straight to chapter 7 and 8, Display, LEDs and buttons and Access rights.
After learning how to use the buttons and menu system, connect power to your Corrigo,
log on as Admin and go to the menu "Configuration".
For the time being, skip the configuration menu In-/Outputs and start by configuring
control functions.
Run through the configuration menus in order and set whatever functions and parameters
you wish to include. Use chapter 6 of this manual for reference.
Keep track of which inputs and outputs you will need. To help you, there is a list of input
and output functions provided in chapter 3, (3.2.3 Input / Output list.)
Finally, configure In-/Outputs.
Exit the "Configuration" menu and go to "Settings".
Set the control values in "Settings".
Set the clock and scheduler functions in "Time Settings".
Set the control setpoints in temperature and air control as well as in humidity control if
humidity control has been configured
Your Corrigo should now be ready to run.