Manual Corrigo Ventilation, revision R Chapter 17 Configuration 99
.No
Alarm text
Pri
Description
28
Analogue deicing
-
Exchanger de-icing activated by de-icing
sensor
29
Rotation sentinel exchanger
B
Exchanger rotation sentinel alarm activated
30
Malfunction fire damper
B
Fire damper exercise test failed
31
Supply air fan control error
-
Supply air pressure deviates too much from
the setpoint for too long.
32
Extract air fan control error
-
Extract air pressure deviates too much from
the setpoint for too long.
33
Supply air fan external
operation
C
SAF run-signal received when unit is
stopped
34
Extract air fan external
operation
C
EAF run-signal received when unit is
stopped
35
Ventilation manual mode
C
The unit is in manual mode
36
Manual supply air control
C
Supply air temp controller in manual control
37
Manual supply air fan mode
C
Supply air fan in manual control
38
Manual supply air fan freq
control
C
The SAF is in manual mode
39
Manual extract air fan mode
C
Extract air fan in manual control
40
Manual extract air fan freq
control
C
The EAF is in manual mode
41
Manual heater control
C
The heater is in manual mode
42
Manual exchanger control
C
Heat exchanger output in manual control
43
Manual cooler control
C
Cooling output in manual control
44
Manual P1 heater
C
Heating circulation pump in manual control
45
Manual P1 exchanger
C
Exchanger circulation pump in manual
control
46
Manual P1 cooler
C
Cooling circulation pump in manual control
47
Manual fire damper
C
Fire dampers in manual control
48
Internal battery error
A
Internal battery needs replacing
49
Sensor error supply air temp
B
Malfunction of connected sensor
50
Sensor error extract air temp
B
Malfunction of connected sensor
51
Sensor error room temp 1
B
Malfunction of connected sensor
52
Sensor error room temp 2
B
Malfunction of connected sensor
53
Sensor error exhaust air temp
B
Malfunction of connected sensor
54
Sensor error extra sensor 1
B
Sensor error Extra sensor 1
55
Sensor error SAF pressure
B
Malfunction of connected sensor
56
Sensor error EAF pressure
B
Malfunction of connected sensor
57
Sensor error deicing temp
B
Malfunction of connected sensor
58
Sensor error frost protection
temp
B
Malfunction of connected sensor
59
Sensor error CO2
B
Malfunction of connected sensor
60
Sensor error humidity room
B
Malfunction of connected sensor
61
Sensor error humidity duct
B
Malfunction of connected sensor
62
Sensor error extra unit temp
B
Malfunction of connected sensor
63
Sensor error external control
SAF
B
Malfunction of connected sensor