Language
If RIGHT is pressed three times when the start menu is shown, a menu is displayed in which
the language can be changed.
The different language files are stored in the application memory and are downloaded to the
work memory. If a Corrigo has been reloaded with a program revision newer than the
factory revision using E tool
©
, the controller will not allow language files to be downloaded
from the application memory. This is because there is a risk that the language files are not
compatible with the new revision. Therefore, you are limited to the two languages you have
downloaded using E tool
©
.
Indication LEDs
Status indication can be found in the upper left corner of the controller. For controllers with
display, the alarm indication and change mode LEDs are located in the keypad area.
Status indication
Changing the battery
Corrigo has an internal battery to ensure the operation of the memory and real-time clock in
the event of a power failure.
When the alarm ”Internal Battery” is activated and the battery LED lights up red, the battery
has become too weak and needs to be changed. Nonetheless, due to a backup capacitor, the
controller will function at least 10 minutes without power supply.
Since changing the battery requires knowledge of proper ESD protection, as well as
dismantling and opening of the unit, this should be handled by skilled service personnel.
Designation Colour Description
Tx Green Port 1/2, transmitting
Rx Green Port 1/2, receiving
Serv (…Lon models) Yellow Service LED LON, commissioning
LAN (…W models) Yellow/Green Green: Connected to other network
equipment
Blinking green: Network traffic
Blinking yellow: For identifying
P/B (Power/Battery) Green/Red Power on/Battery error
Controllers with built-in display:
Red Alarm indication. Flashing: There are
unacknowledged alarms. Fixed: There are
alarms which have been acknowledged but
where the fault remains.
Yellow Change mode. Flashing rapidly: The
display contains changeable values.
Flashing slowly: A password is needed to