CORRIGO VENTILATION 3.X USER GUIDE
Table Of Contents
- About this user guide
- About Corrigo
- Display, buttons and LEDs
- The menu system
- Navigating the menus
- Running mode
- Temperature
- Setpoint Supply air temperature control
- Setpoint Outdoor temperature compensated Supply air control
- Setpoint Cascaded room temperature control
- Setpoint Cascaded extract air temperature control
- Setpoint Outdoor compensated room temperature/extract air control
- Support control heating/Support control cooling
- Frost protection temperature
- Exchanger de-icing
- Heat exchanger efficiency monitoring
- Recirculation
- Extra controller unit
- Enthalpy control
- Air control
- Pressure control SAF (there are also corresponding menus for EAF)
- Flow control SAF (there are also corresponding menus for EAF)
- Manual frequency control SAF (there are also corresponding menus for EAF)
- Frequency control external
- Frequency control SAF with EAF slave/flow control (also available for opposite function)
- CO2
- Humidity control
- Time settings
- Access rights
- Other functions
- Index
Corrigo ventilation user guide, revision F The menu system
9
Shows the accumulated running times for the fans.
Selected functions
In these menus, you can see how some of the most
important functions have been configured. Changes
cannot be made.
Heater, exchanger and cooling type.
If one of the functions is not used, it will be shown as
”Not used”.
This function is used during the summer to cool the
building night-time using cool outdoor air, thereby
reducing the need for cooling during the day and saving
energy.
Support control is used for adjusting the room
temperature outside of the normal running time. If there
is a heating or cooling demand in the room, the unit will
start and the temperature will be adjusted.
The fire function determines the settings for the fire
dampers and the unit’s running mode when a fire alarm
is activated.
Frost protection is normally always used in water
heating systems. The cooling recovery function starts the
heat exchanger in order to return cooling from the
extract air when the extract air is colder than the outdoor
air and cooling is required.
An analogue input can be configured for an external
setpoint device e.g. TG-R4/PT1000.
Running time
SAF: 14.6 h
EAF: 14.4 h
Control function
Supply air control
Fan control
Pressure
Heating: Water
Exchanger: Plate exc
Cooling: Water
Free cool active: No
Support control
active: Yes
CO2/VOC active
If timer on
Fire damper function
Not active
Operation when alarm
Stopped
Frost protection
Active
Cooling recovery
Not active
External setpoint
Not active