Corrigo ventilation Communication Guide 3.3 manu

10 Commonly used signals Communication guide
Signal name
EXOL type
Modbus address
BACnet
Default value
Function Description
VentSettings.Cor_
HeatCoilAutoMode
(0)
X 377 - 2 Manual/Auto Running mode Heating:
0=Off
1=Manual
2=Auto
VentSettings.Cor_
HeatCoilManual(0)
R 378 - 0 Manual/Auto Heating controller output
if manual mode
VentSettings.Cor_E
xchCoilAutoMode
X 379 - 2 Manual/Auto Running mode Exchanger:
0=Off
1=Manual
2=Auto
VentSettings.Cor_E
xchCoilManual
R 380 - 0 Manual/Auto Exchanger controller
output if manual mode
VentSettings.Cor_C
oolCoilAutoMode
X 381 - 2 Manual/Auto Running mode Cooling:
0=Off
1=Manual
2=Auto
VentSettings.Cor_C
oolCoilManual
R 382 - 0 Manual/Auto Cooling controller output
if manual mode
VentSettings.Cor_
HumidityPID_Selec
t
X 383 - 2 Manual/Auto Running mode
Humidification/Dehumidif
ication:
0=Off
1=Manual
2=Auto
VentSettings.Cor_
HumidityPID_Man
Set
R 384 - 0 Manual/Auto Humidification/Dehumidif
ication controller output if
manual mode
VentSettings.Cor_
HeatPumpAutoMod
e(0)
X 385 - 2 Manual/Auto
Running mode P1-
Heating:
0=Manual off
1=Manual on
2=Auto
VentSettings.Cor_E
xchPumpAutoMode
X 386 - 2 Manual/Auto Running mode P1-
Exchanger:
0=Manual off
1=Manual on
2=Auto
VentSettings.Cor_C
oolPumpAutoMode
X 387 - 2 Manual/Auto Running mode P1-
Cooling:
0=Manual off
1=Manual on
2=Auto
VentSettings.Cor_F
ireDamperAutoMo
de
X 388 - 2 Manual/Auto Running mode fire
damper:
0=Close
1=Open
2=Auto