Corrigo ventilation Communication Guide 3.3 manu

Communication guide Commonly used signals 11
Signal name
EXOL type
Modbus address
BACnet
Default value
Function Description
VentSettings.Cor_E
xternalControl
X 451 MSV,
30451
2 Manual/Auto External control:
Modbus:
0=Extended run full speed
1=External stop
2=No external control
3=External stop with
support control
BACnet:
1=Extended run full speed
2=External stop
3=No external control
4=External stop with
support control
3.4 Input Registers
Input register values are read-only.
Signal name
EXOL type
Modbus address
BACnet
Default value
Function Description
VentActual.Cor_Ou
tdoor temp(0)
R 1 AV,
40001
Actual/Setpoint Outdoor temperature
(read-only)
VentActual.Cor_Ef
ficiency
R 2 AV,
40002
Actual/Setpoint Efficiency in % for
exchanger