Corrigo ventilation Communication Guide 3.3 manu

Communication guide Commonly used signals 13
Signal name
EXOL type
Modbus address
BACnet
Default value
Function Description
VentActual.Cor_C
O2Sensor
R 17 AV,
40017
CO2 CO2 (ppm)
VentActual.Cor_Fr
ostprotectionTemp
R 19 AV,
40019
Frost protection Frost protection temp
VentActual.Cor_De
IcingTemp
R 21 AV,
40021
Extract air
temp/De-icing
exchanger
De-icing temp
exchanger
VentActual.Cor_Hu
midityRoom
R 23 AV,
40023
Humidity Humidity room
VentActual.Cor_Ex
traSensor
R 25 AV,
40025
Additional sensor/
External setpoint
Extra sensor 1/External
setpoint (depending on
configuration)
VentActual.Cor_He
atCV1(0)
R 119 AV,
40119
Analogue outputs Control signal heating
Y1 (0...10 V)
VentActual.Cor_Ex
chCV1
R 120 AV,
40120
Analogue outputs Control signal
exchanger Y2 (0...10
V)
VentActual.Cor_Co
olCV1
R 121 AV,
40121
Analogue outputs Control signal cooler
Y3 (0...10 V)
VentActual.Cor_S
AF
R 122 AV,
40122
SAF/EAF
Pressure and Flow
Control signal supply
air fan (0...10 V)
VentActual.Cor_E
AF
R 123 AV,
40123
SAF/EAF
Pressure and Flow
Control signal extract
air fan (0...10 V)
VentActual.Cor_Un
itRunMode
X 284 MSV,
40284
Actual/Setpoint Unit run mode:
Modbus:
0=Off
1=Reduced speed
2=Normal speed
3=Stop because of
alarm
BACnet:
1=Off
2=Reduced speed
3=Normal speed
4=Stop because of
alarm
VentActual.Cor_Fil
terGuard1AI
R 301 AV,
40301
Actual/Setpoint Analogue filter 1 value
(Pa)
VentActual.Cor_Fil
terGuard2AI
R 302 AV,
40302
Actual/Setpoint
Analogue filter 2 value
(Pa)