Corrigo ventilation Communication Guide 3.3 manu

Communication guide Commonly used signals 9
3.3 Holding Register Manual / Auto settings
Signal name
EXOL type
Modbus address
BACnet
Default value
Function Description
VentSettings.Cor_
AirUnitAutoMode
X 368 MSV,
30368
3 Manual/Auto Running mode air unit:
Modbus:
0=Manual off
1=Manual reduced speed
2=Manual normal speed
3=Auto
BACnet:
1=Manual off
2=Manual reduced speed
3=Manual normal speed
4=Auto
VentSettings.Cor_S
upplyPID_Select
X 369 - 2 Manual/Auto Supply temp controller
mode:
0=Manual off
1=Manual on
2=Auto
VentSettings.Cor_S
upplyPID_ManSet
R 370 - 0 % Manual/Auto Supply temp controller
output if manual on mode
VentSettings.Cor_S
AFAutoMode(0)
X 371 - 3 Manual/Auto Running mode SAF:
0=Off
1=Manual half speed
2=Manual full speed
3=Auto
VentSettings.Cor_E
AFAutoMode
X 372 - 3 Manual/Auto Running mode EAF:
0=Off
1=Manual half speed
2=Manual full speed
3=Auto
VentSettings.Cor_S
AFFrequenceAuto
Mode
X 373 - 3 Manual/Auto
Running mode frequence
controlled SAF
0=Manual
1=Man. half speed
2=Man. Fullspeed
3=Auto
VentSettings.Cor_S
AFManual
R 374 - 0 % Manual/Auto Freguencer controller
output SAF if manual
mode
VentSettings.Cor_E
AFFrequenceAuto
Mode
X 375 - 3 Manual/Auto Running mode frequence
controlled EAF
0=Manual
1=Man. half speed
2=Man. Fullspeed
3=Auto
VentSettings.Cor_E
AFManual
R 376 - 0 % Manual/Auto Freguencer controller
output EAF if manual
mode