5.4 Troubleshooting
Should problems occur, please check or correct the following before contacting your service representative.
Always check if there are any alarms active in the control panel. See section 4.3 to learn how to navigate
through the control panel menu. For more information on the alarm designations go to the Systemair
website(www.systemair.com/na/North-America/)anddownloadthecontrollerusermanual.
1. Fan(s) do not start
Check if there are any alarm messages
CheckiftheautomaticfuseAS1istripped(gure3,pos.8)
Checkiffan(s)thermalcontactistrippedduetooverheating(showsas“Fanalarm”inthecontrol
panel).
Checktherunstatusandthesettingincontrolpanel(schedules,auto/manualoperation,airowset
points, etc.)
2. Wheel motor does not start
Check if there are any alarm messages
CheckiftheautomaticfuseAS1istripped(gure3,pos.8)
CheckifthefusesinthefuseholdersF1&F2areblown(gure3,pos.13)
Check the run status and the setting in control panel (schedule, auto/manual operation, free cooling
active, etc.)
3. Reduced Airow
Check if there are any alarm messages
Checktherunstatusandthesettingincontrolpanel(schedules,auto/manualoperation,airowset
points, etc.)
Check if outdoor/exhaust air damper (if used) are opened
Checkifltersneedtobechanged
Check if diffuser/louvers are opened
Check if diffusers/louvers need cleaning
Check if fans and/or exchanger need to be cleaned
Check for obstruction at the air inlets/outlets
Check ducts for visible damage and/or buildup of dust and debris
4. Cold supply air
Check if there are any alarm messages
Check the supply air temperature set point on the control panel
Ifelectricre-heaterisequipped,checkiftheautomaticfuseAS2istripped(gure3,pos.9)
Ifelectricre-heaterisequipped,checkiftheoverheatingthermostatistripped.Ifso,seesection2.2.6
Ifhydronicre-heaterisequipped,checkifthevalve(s)/actuator(s)controllingthewateroware
functioning properly
Checkifltersneedtobechanged
5. Noise/vibrations
Check if the unit is completely leveled
Check if fans and/or exchanger need to be cleaned
Check if the screws holding the fans are tightened properly
5.4.1 Alarms
Thealarmbutton(pos.1,gure3)opensthealarmqueue.Whenpressingthisbuttonactiveand
non-acknowledgedalarmswillbedisplayedinthemenuwindow.Thealarm-LED(pos.2,gure4)willash
iftherearenon-acknowledgedalarmsandbeon(butnotashing)ifthealarmsarestillactivebuthave
beenacknowledged.Iftherearemultiplealarms,useUP/DOWNtomovebetweenthem.Analarmcanbe
acknowledgedorblockedbyusingOKandUP/DOWN.Toabortandgobacktostartmenupresscancel
and then press LEFT.
See Commissioning record for an overview of possible alarms.