400896 Topvex FR Installation Instructions

Topvex FR800, FR1600, FR3800
Installation instructions
Systemair Inc.
6
3.2 Where/How to Install
The unit is meant for indoor installation. It is important that the unit is completely level before it is put into
operation. The electronic components should not be exposed to lower temperature than 32° F (0° C) or
higher than +122° F (+50° C).
When choosing the location, keep in mind that the unit requires maintenance regularly and that the
inspection doors should be easily accessible. Leave free space for opening the doors and for taking out the
main components (Figure 2)
Note:
If there is not sufcient space to open the inspection doors it is possible to unscrew the hinges to remove
the doors completely for inspection and maintenance. Another option, when installing the unit suspended
with the inspection door facing downwards, is to acquire the sliding door accessory kit.
Avoid placing the appliance against a wall, as low frequency noise can cause vibrations in the wall even id
the fan noise-level is acceptable. If this is not possible it is recommended to carefully insulate the wall.
The outdoor air intake of the building should if possible be put in the northern or eastern side of the building
and away from other exhaust outlets like kitchen fan outcasts or laundry room outlets. The extract air
should ideally be led out via a roof cowl away from any outdoor air intakes, windows, balconies etc.
Warning
• The unit must be duct connected or in some other way provided with protection so that it is not
possible to come into contact with the fans through the duct connections.
1 Warnings
The following admonitions will be presented in the different sections of the document.
Danger
Make sure that the Mains supply to the unit is disconnected before performing any maintenance or
electrical work!
All electrical connections must be carried out in accordance with local rules and regulations.
Warning
In order for the unit to be considered safely installed the doors if equipped with handles have to be
locked with a key to prevent unauthorized or accidental opening
The unit must be duct connected or in some other way provided with protection so that it is not
possible to come in contact with the fans through the duct connections
The unit is heavy. Be careful during transport and mounting. Risk of injury through pinching. Use
protective clothing.
Beware of sharp edges during mounting and maintenance. Make sure that a proper lifting device is
used. Use protective clothing.
Caution
If the unit is installed in a cold place make sure that all joints are covered with insulation, and tape well
Duct connections/duct ends should be covered during storage and installation
Do not connect tumble dryers to the ventilation system
Take care not to damage the water battery when connecting water pipes to connectors. Use a
spanner to tighten the connection.
Topvex FR03, FR06, FR08, and FR11
Installation instructions
206638
1
Systemair AB
3 Installation
3.1 Unpacking
Topvex FR800-3800 are delivered on a pallet (gure 3 and gure 4). Handles and necessary components
are placed inside the unit.
The inspection hatches are opened by the use of a 5/8” (16 mm) cap key (gure 5). To facilitate opening
and closing of the inspection hatches, install the 4 handles that are placed inside the unit on delivery (8
handles if sliding door option is used).
Verify that all ordered equipment is delivered before starting the installation. Any discrepancies from the
ordered equipment must be reported to the supplier of Systemair products.
Fig. 5 Opening inspection hatches with a cap key
Warning
The door handles must be locked before the unit is put into operation to ensure the required level of
safety for the unit. (Hex size: 5/16 in (8 mm)
1 Warnings
The following admonitions will be presented in the different sections of the document.
Danger
Make sure that the Mains supply to the unit is disconnected before performing any maintenance or
electrical work!
All electrical connections must be carried out in accordance with local rules and regulations.
Warning
In order for the unit to be considered safely installed the doors if equipped with handles have to be
locked with a key to prevent unauthorized or accidental opening
The unit must be duct connected or in some other way provided with protection so that it is not
possible to come in contact with the fans through the duct connections
The unit is heavy. Be careful during transport and mounting. Risk of injury through pinching. Use
protective clothing.
Beware of sharp edges during mounting and maintenance. Make sure that a proper lifting device is
used. Use protective clothing.
Caution
If the unit is installed in a cold place make sure that all joints are covered with insulation, and tape well
Duct connections/duct ends should be covered during storage and installation
Do not connect tumble dryers to the ventilation system
Take care not to damage the water battery when connecting water pipes to connectors. Use a
spanner to tighten the connection.
Topvex FR03, FR06, FR08, and FR11
Installation instructions
206638
1
Systemair AB