Corrigo ventilation 3.4 manu

Manual Corrigo Ventilation, revision R Chapter 13 Time settings 71
If you want to run the unit from one day to another, e.g. from Mon 22:00 to Tue 09:00, the desired
running time for both days must be entered.
Normal speed
Monday
Per 1: 07:00 16:00
Per 2: 22:00 - 24:00
Normal speed
Tuesday
Per 1: 00:00 09:00
Per 2: 00:00 - 00:00
13.3 Timer Reduced speed
These settings will be ignored if single speed fans are configured.
Should periods for normal speed and periods for reduced speed overlap, normal speed takes
precedence.
There are eight separate setting menus, one for each weekday and one extra for holidays. Holiday
schedules take precedence over other schedules. For 24 hour running, set a period to 00:00 24:00.
To disable a period, set it to 00:00 00:00. If both periods of a day are set to 00:00 00:00, the unit
will not run at "Reduced speed" that day.
Reduced speed
Sunday
Per 1: 10:00 16:00
Per 2: 00:00 - 00:00
13.4 Extended running
Digital inputs can be used to force the unit to start although the timer says the running mode should
be “Off”.
For 2-speed fans and pressure/flow controlled fans, inputs for normal speed and reduced speed can
normally be used.
The unit will run for the set time. If the running time is set to zero the unit will only run as long as
the digital input is closed.
Extended running
60 min
Time in ext Running
0 min
13.5 Timer outputs 1…5
Up to 5 digital outputs can be used as timer controlled outputs. Each with individual week-
schedules with two activation periods per day. Each output has eight separate setting menus, one for
each weekday and one extra for holidays. Holiday schedules take precedence over other schedules.
Only the time channels which have been configured, i.e. have been wired to a digital output, will be
shown.
Timer output2
Wednesday
Per 1: 05:30 08:00
Per 2: 17:00 23:00
If the function "Recirculation" has been configured (see 5.1.11), "Timer output 5" can be used to
control start/stop of the recirculation function.