CORRIGO VENTILATION 3.X USER GUIDE
Table Of Contents
- About this user guide
- About Corrigo
- Display, buttons and LEDs
- The menu system
- Navigating the menus
- Running mode
- Temperature
- Setpoint Supply air temperature control
- Setpoint Outdoor temperature compensated Supply air control
- Setpoint Cascaded room temperature control
- Setpoint Cascaded extract air temperature control
- Setpoint Outdoor compensated room temperature/extract air control
- Support control heating/Support control cooling
- Frost protection temperature
- Exchanger de-icing
- Heat exchanger efficiency monitoring
- Recirculation
- Extra controller unit
- Enthalpy control
- Air control
- Pressure control SAF (there are also corresponding menus for EAF)
- Flow control SAF (there are also corresponding menus for EAF)
- Manual frequency control SAF (there are also corresponding menus for EAF)
- Frequency control external
- Frequency control SAF with EAF slave/flow control (also available for opposite function)
- CO2
- Humidity control
- Time settings
- Access rights
- Other functions
- Index
The menu system Corrigo ventilation user guide, revision F
16
Air control
This menu is only shown if frequency controlled fans have been configured.
Depending on the choice of fan control, different combinations of the menus below will be
shown.
Pressure control SAF (there are also corresponding menus for EAF)
Here, Actual and Setpoint values are displayed. This is a
read-only menu. No settings can be made here.
Submenu Setpoint values for normal speed (1/1)
and reduced speed (1/2).
Submenu outdoor compensation. An outdoor
temperature dependent compensation of the
pressure setpoint value can be added. The
compensation can be set for either the supply air
fan alone or for both fans.
Submenu extra compensation. A
temperature dependent compensation
similar to the one above but with
selectable temperature source.
Flow control SAF (there are also corresponding menus for EAF)
Setpoint Flow control. Here, Actual and Setpoint values
are displayed. This is a read-only menu. No settings can
be made here.
Submenu Setpoint values for normal speed (1/1)
and reduced speed (1/2).
Submenu Outdoor compensation. An outdoor
temperature dependent compensation of the
pressure setpoint value can be added. The
compensation can be set for either the supply air
fan alone or for both fans.
Pressure control SAF
Actual: 480 Pa
Setp: 490 Pa
Pressure control SAF
Setp 1/1: 490 Pa
Setp 1/2: 300 Pa
Outdoor comp setp
-20 °C = -50 Pa
10 °C = 0 Pa
Act comp: -5 Pa
Comp sens:Room temp1
15 °C = 0 Pa
20 °C = 0 Pa
25 °C = 0 Pa
Flow control SAF
Actual: 1800 m3/h
Setp: 2000 m3/h
Flow control SAF
Setp 1/1: 2000 m3/h
Setp 1/2: 1000 m3/h
Outdoor comp setp
-15 °C =-200.0 m3/h
10 °C = 0.0 m3/h
Act comp: 0.0 m3/h