CORRIGO VENTILATION 3.X USER GUIDE
Table Of Contents
- About this user guide
- About Corrigo
- Display, buttons and LEDs
- The menu system
- Navigating the menus
- Running mode
- Temperature
- Setpoint Supply air temperature control
- Setpoint Outdoor temperature compensated Supply air control
- Setpoint Cascaded room temperature control
- Setpoint Cascaded extract air temperature control
- Setpoint Outdoor compensated room temperature/extract air control
- Support control heating/Support control cooling
- Frost protection temperature
- Exchanger de-icing
- Heat exchanger efficiency monitoring
- Recirculation
- Extra controller unit
- Enthalpy control
- Air control
- Pressure control SAF (there are also corresponding menus for EAF)
- Flow control SAF (there are also corresponding menus for EAF)
- Manual frequency control SAF (there are also corresponding menus for EAF)
- Frequency control external
- Frequency control SAF with EAF slave/flow control (also available for opposite function)
- CO2
- Humidity control
- Time settings
- Access rights
- Other functions
- Index
The menu system Corrigo ventilation user guide, revision F
20
Humidity control
This menu is only shown if humidity control has been configured.
Humidity sensor room
Humidity control can be configured as either
Humidification or Dehumidification or as combined
Humidification/Dehumidification.
Humidity sensor duct
A duct humidity sensor is only used for maximum
limitation function.
Time settings
General
Corrigo has a year-base clock function. This means that
a week-schedule with holiday periods for a full year can
be set.
The clock has an automatic summertime/wintertime
change-over.
Individual schedules for each week-day plus a separate
holiday setting. Up to 24 individual holiday periods can
be configured. A holiday period can be anything from
one day up to 365 days. Holiday schedules take
precedence over other schedules.
Each day has up to two individual running periods. For two-speed fans and pressure
controlled fans there are daily individual schedules for normal speed and reduced speed, each
with up to two running periods.
Up to 5 digital outputs can be used as timer controlled outputs. Each with individual week-
schedules with two activation periods per day. These outputs can be used to control lighting,
door locks etc. Only outputs which have been configured will be shown. Timer output 5 can
be used to control a recirculation function.
Time/Date
This menu shows and permits the setting of time and
date.
Time is shown in 24-hour format.
Date is shown in the format YY-MM-DD.
Humidity room
Actual: 51.9% RH
Setp: 50.0% RH
Humidity duct
Actual: 72.2% RH
Max limit: 80.0% RH
Hyst: 20.0% RH
Time/Date
Timer normal speed
Timer reduced speed
Extended running
Timer output1
Timer output2
Timer output3
Timer output4
Timer output5
Holidays
Current time: 18:21
Date: 2016-11-10
Weekday: Monday