CORRIGO VENTILATION 3.X USER GUIDE
Table Of Contents
- About this user guide
- About Corrigo
- Display, buttons and LEDs
- The menu system
- Navigating the menus
- Running mode
- Temperature
- Setpoint Supply air temperature control
- Setpoint Outdoor temperature compensated Supply air control
- Setpoint Cascaded room temperature control
- Setpoint Cascaded extract air temperature control
- Setpoint Outdoor compensated room temperature/extract air control
- Support control heating/Support control cooling
- Frost protection temperature
- Exchanger de-icing
- Heat exchanger efficiency monitoring
- Recirculation
- Extra controller unit
- Enthalpy control
- Air control
- Pressure control SAF (there are also corresponding menus for EAF)
- Flow control SAF (there are also corresponding menus for EAF)
- Manual frequency control SAF (there are also corresponding menus for EAF)
- Frequency control external
- Frequency control SAF with EAF slave/flow control (also available for opposite function)
- CO2
- Humidity control
- Time settings
- Access rights
- Other functions
- Index
Corrigo ventilation user guide, revision F The menu system
19
CO
2
In applications with varying occupancy, the fan speed
can be controlled by the air quality as measured by a
CO
2
sensor. CO
2
can be set to function either on Y2, Y4
or both.
Controller output
comp if cooling
0 at R U S= 0 %
100 at R U S= 0 %
Controller output
comp if heating
0 at R U S= 0 %
100 at R U S= 0 %
Controller output
compensation
Not active
Compensation only
when
1/1-speed : No
defrosting: No
CO2
Actual:920ppm
Setp:1000pm