SAVE MODBUS VARIABLE LIST 20210301 REV36
Table Of Contents
- 1 Information
- 2 Modbus variable list
- 2.1 Demand Control
- 2.2 User modes
- 2.3 Airflow Control
- 2.4 Outdoor Airflow Compensation
- 2.5 Temperature Control
- 2.6 Cooler
- 2.7 Heater
- 2.8 Extra Controller
- 2.9 Change-over (Heating/Cooling)
- 2.10 Moisture transfer control
- 2.11 Cooling recovery
- 2.12 ECO mode
- 2.13 Free Cooling
- 2.14 Week Schedule
- 2.15 Time and Date
- 2.16 Filter replacement
- 2.17 Analog Input values (Temperatures, CO2, RH)
- 2.18 Digital Input functions
- 2.19 Output values
- 2.20 Alarms
- 2.21 System settings
- 2.22 Modbus
- 2.23 Unit Backups
- 3 Revision table
4
| Modbus variable list
Symbolic register name
Sig.
Modbus Reg. type Mod-
bus
Adr.
Min Max Description
REG_USERMODE_MODE I
Read Input Register
(Function 04)
1161 0 12
Active User mode.
0: Auto
1: Manual
2: Crowded
3: Refresh
4: Fireplace
5: Away
6: Holiday
7: Cooker Hood
8: Vacuum Cleaner
9: CDI1
10: CDI2
11: CDI3
12: PressureGuard
REG_USERMODE_HMI_CHANGE_
REQUEST
I
Holding Register
(Function 03/06/16)
1162 0 7
New desired user mode as requested by
HMI
0: None
1: AUTO
2: Manual
3: Crowded
4: Refresh
5: Fireplace
6: Away
7: Holiday
REG_CDI_1_AIRFLOW_LEVEL_SAF I
Holding Register
(Function 03/06/16)
1171 0 5
Fan speed level for configurable digital input
1.
0: Off
1: Minimum
2: Low
3: Normal
4: High
5: Maximum
REG_CDI_1_AIRFLOW_LEVEL_EAF I
Holding Register
(Function 03/06/16)
1172 0 5
Fan speed level for configurable digital input
1.
0: Off
1: Minimum
2: Low
3: Normal
4: High
5: Maximum
REG_CDI_2_AIRFLOW_LEVEL_SAF I
Holding Register
(Function 03/06/16)
1173 0 5
Fan speed level for configurable digital input
2.
0: Off
1: Minimum
2: Low
3: Normal
4: High
5: Maximum
REG_CDI_2_AIRFLOW_LEVEL_EAF I
Holding Register
(Function 03/06/16)
1174 0 5
Fan speed level for configurable digital input
2.
0: Off
1: Minimum
2: Low
3: Normal
4: High
5: Maximum
REG_CDI_3_AIRFLOW_LEVEL_SAF I
Holding Register
(Function 03/06/16)
1175 0 5
Fan speed level for configurable digital input
3.
0: Off
1: Minimum
2: Low
3: Normal
4: High
5: Maximum
REG_CDI_3_AIRFLOW_LEVEL_EAF I
Holding Register
(Function 03/06/16)
1176 0 5
Fan speed level for configurable digital input
3.
0: Off
1: Minimum
2: Low
3: Normal
4: High
5: Maximum
| 2.1