SAVE VTR 150K INSTALLATIONV01 20210316

10
| Electrical connections
Position Description
8
Analog input 2 Supply air sensor
9
Analog input 3 Freely configurable
10
Analog input 4 Freely configurable / Overheat temperature sensor (units with
heater)
11
Analog input 5 Freely configurable
12
Digital input 1 Rotor guard sensor (only for VSR, VTR models)
13
Digital input 2 Freely configurable / Cooker hood (VTR 150/K unit)
14
Analog output 2 Freely configurable / Electrical heater controller (VTC 700 unit)
15
Analog output 1 Rotary heat exchanger control signal (for VSR, VTR type models) /
Damper control signal (for VTC, VSC type models), UI6 Bypass damper feedback
signal (for VTC, VSC type models)
16
Terminals for speed control of extract air fan
17
Terminals for speed control of supply air fan
7.2 External connections (Connection board)
External connections to the main circuit board are done via connection board situated inside of the unit.
Fig. 6 External connection box and board
Position Description
1
Connection to the main circuit board
2
Connection for external control panel (HMI) or Internet access module (IAM)
3
Modbus RS485 connection
AI6–7
Freely configurable Analog input. None/Input type selection in HMI.
DO1–4
Freely configurable digital output.
DO2 default configuration: Outdoor-/Exhaust Air Damper
DO3 default configuration: Activate Cooling
DO4 default configuration: Sum Alarm
AO3–5
Freely configurable analog output. Actuator type 0–10V, 10–0V, 2–10V, 10–2V.
AO3 default configuration: Heating (only for VTC 200/300/500/700, VTR 100/700 type models).
AO4 default configuration: Cooling
254494 | v01