SAVE VTR 150K SERVICE AND ACCESSORIES INSTALLATIONV01 20210316

34
|
Accessories
4. Configure room temperature sensor: Go to Input menu. Select ANALOG tab. Select the analog input to which the
sensor is connected. Example if it is connected to AI6 on the connection board, then select ANALOG INPUT 6. Select
input type as Room Air Temperature Sensor (RAT).
5.3 Temperature control
5.3.1 Electric duct heater (control via relay)
The electric heater can be installed in outdoor or supply air ducts.
RL
230 V~
DO
AI
ECT
ELH
AI
SAT
ELH
RL
230 V~
DO
SAT
T
ECT
ELH
4
3
1
2
AI
ELH electric heater
ECT extra controller temperature sensor
OAT outdoor air duct temperature sensor
SAT supply air temperature sensor
RL relay
1 Outdoor air
2 Supply air
3 Extract air
4 Exhaust air
Component/product Article number:
CB 125-0,6 230V/1 Duct heater 5289
CB Preheater Connection Kit 142852
5.3.1.1 Heater installed in the outdoor air duct
Installation and connection
1. Install an electric heater (ELH) at least 100 mm distance
from the unit in the outdoor air duct. A relay (RL) is
used to control the heater. Connect relay to any free
digital output on the connection board (CB).
2. Connect the power supply to the electric heater via a
relay. A circuit breaker (BRK) is not included in the
package and must be ordered separately. It must be in-
stalled in the circuit.
3. Install a duct temperature sensor (OAT) before the
electric heater and connect it to any free analog input
on the connection board (CB).
Outdoor air heater configuration
1. Go to Service menu
2. Enter password (default 1111)
3. Set the heater type: Components —> Extra Controller —>Extra Controller Mode —> Preheater.
4. Configure connection of the pre-heater. Go to Service menu. Select Output menu. In next menu select DIGITAL
tab. Select the digital output to which the pre-heater is connected. Example if it is connected to DO3 on the connec-
tion board, then select DIGITAL OUTPUT 3 and select Step Controller Y4 Extra Controller from the output
type list.