SAVE VTR 150K SERVICE AND ACCESSORIES INSTALLATIONV01 20210316

36
|
Accessories
5. Configure the installed sensor. Go to menu Service > Input > ANALOG. Select the analog input to which the sensor
is connected. Example if it is connected to AI6 on the connection board, then select ANALOG INPUT 6 > Extra Con-
troller Temp. Sensor (ECT).
5.3.2 Duct water heater
A duct water heating battery is supposed to be installed in supply air duct.
WH water heating battery
FPT frost protection sensor
SAT supply air temperature sensor
S actuator for valve
1 Outdoor air
2 Supply air
3 Extract air
4 Exhaust air
Component/product Article number:
VBC 125-2 Water heating battery (2 rows) 5457
VBC 125-3 Water heating battery (3 rows) 9839
VAZ4 24A Actuator 0-10V (S) 9862
ZTV 15-0,4 2-way valve 9829
ZTV 15-0,6 2-way valve 6571
ZTR 15-0,4 valve 3-way 9670
ZTR 15-0,6 valve 3-way 6573
Duct sensor -30-70C (SAT) 211524
Surface sensor -30-150C (FPT) 211523
Transformer 24V 202692
Fig. 11 Water heater connections
Installation and connection
1. Install water heater in the duct. Connect pipes, 2/3–
way valve and actuator.
Important
Do NOT use 24V DC power output from the
connection board for valve actuator.
2. Connect actuator (S) to any free analog output.
3. The frost protection sensor (FPT) should be strapped on a surface on the return water pipe. Connect FPT sensor to
any free analog input.
4. An internal supply air temperature sensor (SAT, default connection AI2 on the main circuit board) must be replaced
by a duct temperature sensor which can be acquired as an accessory. A duct temperature sensor must be installed in
the duct after water heater. Connect the duct temperature sensor to analog input 2 (AI2) replacing the internal supply
air temperature sensor.
Note:
A duct temperature sensor can be connected to analog inputs 6–7 on the connection board for better
access and then configured as a supply air temperature sensor. However the internal supply air
temperature sensor must be disabled in the control panel first.
Configuration
1. Go to Service menu
2. Enter password (default 1111)
| v1.1