SAVE VTR 150K SERVICE AND ACCESSORIES INSTALLATIONV01 20210316

Accessories
|
33
Table 5 LED indicator codes
WLAN
Ethernet Cloud
RED LED GREEN LED
Connected
Not Connected Blinks fast
Disconnected
Disconnected Blinks slow
Connected
Connected
Blinks slow
Connected Not Connected
Blinks fast
Disconnected Disconnected
Blinks fast
Connected Connected
Blinks slow
Fast blinking every 500 milliseconds. Slow blinking every 2 seconds.
5.2 Indoor air quality sensors
Indoor air quality sensors (IAQ) are CO
2
, relative humidity and temperature
transmitters that must be installed either in extract air duct or the room de-
pending on the type of transmitter.
IAQ indoor air quality sensor (CO
2
, RH and
temperature)
CO2 CO
2
duct sensor
1 Outdoor air
2 Supply air
3 Extract air
4 Exhaust air
Component/product Article number:
Systemair-1 CO2 duct sensor 14906
Systemair-E CO2 sensor 14904
Room sensor 0-50C (temperature) 211525
Systemair-E CO2 RH Temperature 211522
Fig. 10 IAQ connections
Installation and connection
1. Install IAQ sensor in the duct or the room depending on
the transmitter type.
2. Connect CO
2
sensor to any free universal analog input
(UI) on the connection board.
3. If IAQ sensor contains relative humidity transmitter:
Connect it to any free universal analog input (UI) on the
connection board.
4. If IAQ sensor contains room temperature transmitter:
Connect it to any free analog input (AI) on the connec-
tion board (only AI6 and AI7 are available on the con-
nection board).
Configuration
1. Go to Service menu.
2. Enter password (default 1111).
3. Configure of CO
2
and/or relative humidity sensor: Go to Input menu. Select UNIVERSAL tab. Select the universal in-
put to which the sensor is connected. Example if it is connected to UI4 on the connection board, then select UNIVER-
SAL INPUT 4. Select signal type as Analog input and select sensor type from the input type list: RH sensor (RH)
and/or CO Sensor (CO).