SAVE MODBUS VARIABLE LIST 20210301 REV36

6
| Modbus variable list
Symbolic register name
Sig.
Modbus Reg. type Mod-
bus
Adr.
Min Max Description
REG_SPEED_PRESSURE_GUARD_SAF I
Read Input Register
(Function 04)
1227
SAF speed value for low fan speed.(1):
Depends on regulation type. Value can be
%, RPM, Pressure or Flow
REG_SPEED_PRESSURE_GUARD_EAF I
Read Input Register
(Function 04)
1228
EAF speed value for low fan speed.(1):
Depends on regulation type. Value can be
%, RPM, Pressure or Flow
REG_USERMODE_REMAINING_TIME_
CDI1_L
I
Read Input Register
(Function 04)
1621 Remaining time
REG_USERMODE_REMAINING_TIME_
CDI1_H
I
Read Input Register
(Function 04)
1622
REG_USERMODE_REMAINING_TIME_
CDI2_L
I
Read Input Register
(Function 04)
1623 Remaining time
REG_USERMODE_REMAINING_TIME_
CDI2_H
I
Read Input Register
(Function 04)
1624
REG_USERMODE_REMAINING_TIME_
CDI3_L
I
Read Input Register
(Function 04)
1625 Remaining time
REG_USERMODE_REMAINING_TIME_
CDI3_H
I
Read Input Register
(Function 04)
1626
REG_FUNCTION_ACTIVE_PRESSURE_
GUARD
I
Read Input Register
(Function 04)
3114 0 1
Indicates if function is active
REG_FUNCTION_ACTIVE_CDI_1 I
Read Input Register
(Function 04)
3115 0 1
Indicates if function is active
REG_FUNCTION_ACTIVE_CDI_2 I
Read Input Register
(Function 04)
3116 0 1
Indicates if function is active
REG_FUNCTION_ACTIVE_CDI_3 I
Read Input Register
(Function 04)
3117 0 1
Indicates if function is active
REG_SENSOR_DI_PRESSURE_GUARD I
Read Input Register
(Function 04)
12316 0 1
Indicates if physical DI is active
REG_SENSOR_DI_CDI_1 I
Read Input Register
(Function 04)
12317 0 1
Indicates if physical DI is active
REG_SENSOR_DI_CDI_2 I
Read Input Register
(Function 04)
12318 0 1
Indicates if physical DI is active
REG_SENSOR_DI_CDI_3 I
Read Input Register
(Function 04)
12319 0 1
Indicates if physical DI is active
2.3 Airflow Control
Symbolic register name
Sig.
Modbus Reg. type Mod-
bus
Adr.
Min Max Description
REG_SENSOR_RPM_SAF I
Read Input Register
(Function 04)
12401 0 5000
Supply Air Fan RPM indication from TACHO
REG_SENSOR_RPM_EAF I
Read Input Register
(Function 04)
12402 0 5000
Extract Air Fan RPM indication from TACHO
REG_SENSOR_FLOW_PIGGYBACK_SAF I
Read Input Register
(Function 04)
12403
Flow value calculated from piggyback
pressure sensor.
REG_SENSOR_FLOW_PIGGYBACK_EAF I
Read Input Register
(Function 04)
12404
Flow value calculated from piggyback
pressure sensor.
REG_SENSOR_DI_BYF I
Read Input Register
(Function 04)
12405
Value from Bypass Damper Feedback input.
In %.
REG_SYSTEM_UNIT_FLOW I
Holding Register
(Function 03/06/16)
9001 0 2
Unit for CAV control mode.0: l/s1: m3/h2:
cfm
REG_SYSTEM_UNIT_PRESSURE I
Holding Register
(Function 03/06/16)
9002 0 1
Units for VAV control mode.0: Pa1: InH2O
REG_MANUAL_OVERRIDE_OUTPUT_SAF I
Holding Register
(Function 03/06/16)
13601 0 1
SAF Override.0: Auto1: Manual
REG_MANUAL_OVERRIDE_OUTPUT_EAF I
Holding Register
(Function 03/06/16)
13602 0 1
EAF Override.0: Auto1: Manual
REG_MANUAL_OVERRIDE_OUTPUT_
SAF_VALUE
I
Holding Register
(Function 03/06/16)
13801 0 100
SAF Override value in % if manual (1)
selected
| 2.1