SAVE MODBUS VARIABLE LIST 20210301 REV36

8
| Modbus variable list
Symbolic register name
Sig.
Modbus Reg. type Mod-
bus
Adr.
Min Max Description
REG_FAN_LEVEL_SAF_HIGH_
PERCENTAGE
I
Holding Register
(Function 03/06/16)
1407 16 100
SAF speed value for high fan speed
REG_FAN_LEVEL_EAF_HIGH_
PERCENTAGE
I
Holding Register
(Function 03/06/16)
1408 16 100
EAF speed value for high fan speed
REG_FAN_LEVEL_SAF_MAX_
PERCENTAGE
I
Holding Register
(Function 03/06/16)
1409 16 100
SAF speed value for maximum fan speed
REG_FAN_LEVEL_EAF_MAX_
PERCENTAGE
I
Holding Register
(Function 03/06/16)
1410 16 100
EAF speed value for maximum fan speed
REG_FAN_LEVEL_SAF_MIN_RPM I
Holding Register
(Function 03/06/16)
1411 500 5000
SAF speed value for minimum fan speed
REG_FAN_LEVEL_EAF_MIN_RPM I
Holding Register
(Function 03/06/16)
1412 500 5000
EAF speed value for minimum fan speed
REG_FAN_LEVEL_SAF_LOW_RPM I
Holding Register
(Function 03/06/16)
1413 500 5000
SAF speed value for low fan speed
REG_FAN_LEVEL_EAF_LOW_RPM I
Holding Register
(Function 03/06/16)
1414 500 5000
EAF speed value for low fan speed
REG_FAN_LEVEL_SAF_NORMAL_RPM I
Holding Register
(Function 03/06/16)
1415 500 5000
SAF speed value for normal fan speed
REG_FAN_LEVEL_EAF_NORMAL_RPM I
Holding Register
(Function 03/06/16)
1416 500 5000
EAF speed value for normal fan speed
REG_FAN_LEVEL_SAF_HIGH_RPM I
Holding Register
(Function 03/06/16)
1417 500 5000
SAF speed value for high fan speed
REG_FAN_LEVEL_EAF_HIGH_RPM I
Holding Register
(Function 03/06/16)
1418 500 5000
EAF speed value for high fan speed
REG_FAN_LEVEL_SAF_MAX_RPM I
Holding Register
(Function 03/06/16)
1419 500 5000
SAF speed value for maximum fan speed
REG_FAN_LEVEL_EAF_MAX_RPM I
Holding Register
(Function 03/06/16)
1420 500 5000
EAF speed value for maximum fan speed
REG_FAN_LEVEL_SAF_MIN_PRESSURE I
Holding Register
(Function 03/06/16)
1421
SAF speed value for minimum fan speed
REG_FAN_LEVEL_EAF_MIN_PRESSURE I
Holding Register
(Function 03/06/16)
1422
EAF speed value for minimum fan speed
REG_FAN_LEVEL_SAF_LOW_PRESSURE I
Holding Register
(Function 03/06/16)
1423
SAF speed value for low fan speed
REG_FAN_LEVEL_EAF_LOW_PRESSURE I
Holding Register
(Function 03/06/16)
1424
EAF speed value for low fan speed
REG_FAN_LEVEL_SAF_NORMAL_
PRESSURE
I
Holding Register
(Function 03/06/16)
1425
SAF speed value for normal fan speed
REG_FAN_LEVEL_EAF_NORMAL_
PRESSURE
I
Holding Register
(Function 03/06/16)
1426
EAF speed value for normal fan speed
REG_FAN_LEVEL_SAF_HIGH_PRESSURE I
Holding Register
(Function 03/06/16)
1427
SAF speed value for high fan speed
REG_FAN_LEVEL_EAF_HIGH_PRESSURE I
Holding Register
(Function 03/06/16)
1428
EAF speed value for high fan speed
REG_FAN_LEVEL_SAF_MAX_PRESSURE I
Holding Register
(Function 03/06/16)
1429
SAF speed value for maximum fan speed
REG_FAN_LEVEL_EAF_MAX_PRESSURE I
Holding Register
(Function 03/06/16)
1430
EAF speed value for maximum fan speed
REG_FAN_LEVEL_SAF_MIN_FLOW I
Holding Register
(Function 03/06/16)
1431
SAF speed value for minimum fan speed
REG_FAN_LEVEL_EAF_MIN_FLOW I
Holding Register
(Function 03/06/16)
1432
EAF speed value for minimum fan speed
REG_FAN_LEVEL_SAF_LOW_FLOW I
Holding Register
(Function 03/06/16)
1433
SAF speed value for low fan speed
REG_FAN_LEVEL_EAF_LOW_FLOW I
Holding Register
(Function 03/06/16)
1434
EAF speed value for low fan speed
REG_FAN_LEVEL_SAF_NORMAL_FLOW I
Holding Register
(Function 03/06/16)
1435
SAF speed value for normal fan speed
REG_FAN_LEVEL_EAF_NORMAL_FLOW I
Holding Register
(Function 03/06/16)
1436
EAF speed value for normal fan speed
| 2.1