SAVE MODBUS VARIABLE LIST 20210301 REV36

16
| Modbus variable list
Symbolic register name
Sig.
Modbus Reg. type Mod-
bus
Adr.
Min Max Description
REG_WS_DAY7_PRD1_ENABLED I
Holding Register
(Function 03/06/16)
5113 0 1
Flag indicating if this period is enabled.
REG_WS_DAY7_PRD2_ENABLED I
Holding Register
(Function 03/06/16)
5114 0 1
Flag indicating if this period is enabled.
2.15 Time and Date
Symbolic register name
Sig.
Modbus Reg. type Mod-
bus
Adr.
Min Max Description
REG_TIME_YEAR I
Holding Register
(Function 03/06/16)
6001 0 2999 Current time
REG_TIME_MONTH I
Holding Register
(Function 03/06/16)
6002 1 12 Current time
REG_TIME_DAY I
Holding Register
(Function 03/06/16)
6003 1 31 Current time
REG_TIME_HOUR I
Holding Register
(Function 03/06/16)
6004 0 23 Current time
REG_TIME_MINUTE I
Holding Register
(Function 03/06/16)
6005 0 59 Current time
REG_TIME_SECOND I
Holding Register
(Function 03/06/16)
6006 0 59 Current time
REG_TIME_AUTO_SUM_WIN I
Holding Register
(Function 03/06/16)
6007 0 1
Flag indicating if DST is enabled.
0: Daylight saving time not enabled
1: Daylight saving time enabled
REG_HOUR_FORMAT I
Holding Register
(Function 03/06/16)
6008 0 1
Indicaties the presentation of time in the
HMI. 24H/12H
REG_DAY_OF_THE_WEEK I
Read Input Register
(Function 04)
6009 0 6
Monday (0)...Sunday (6)
REG_DST_PERIOD_ACTIVE I
Read Input Register
(Function 04)
6010 0 1
REG_TIME_RTC_SECONDS_L I
Read Input Register
(Function 04)
6011
Now time in seconds. Lower 16 bits.
REG_TIME_RTC_SECONDS_H I
Read Input Register
(Function 04)
6012
Now time in seconds. Higher 16 bits.
REG_SYSTEM_START_UP_TIME_L I
Read Input Register
(Function 04)
6021
REG_SYSTEM_START_UP_TIME_H I
Read Input Register
(Function 04)
6022
REG_TIME_RTC I
Read Input Register
(Function 04)
6101
RTC value in seconds, highest 16 bits
2.16 Filter replacement
Symbolic register name
Sig.
Modbus Reg. type Mod-
bus
Adr.
Min Max Description
REG_FILTER_PERIOD I
Holding Register
(Function 03/06/16)
7001 3 15
Filter replacement time in months
REG_FILTER_REPLACEMENT_TIME_L I
Holding Register
(Function 03/06/16)
7002
Timestamp of latest filter replcement, lower
16 bits
REG_FILTER_REPLACEMENT_TIME_H I
Holding Register
(Function 03/06/16)
7003
Timestamp of latest filter replcement,
higher 16 bits
REG_FILTER_PERIOD_SET I
Read Input Register
(Function 04)
7004
Indicates that the
LastFilterReplacementTime shall be set
Now.
REG_FILTER_REMAINING_TIME_L I
Read Input Register
(Function 04)
7005
Remaining filter time in seconds, lower 16
bits.
REG_FILTER_REMAINING_TIME_H I
Read Input Register
(Function 04)
7006
Remaining filter time in seconds, higher 16
bits.
| 2.1