SAVE MODBUS VARIABLE LIST 20210301 REV36

22
| Modbus variable list
Symbolic register name
Sig.
Modbus Reg. type Mod-
bus
Adr.
Min Max Description
REG_ALARM_EXTRA_CONTROLLER_
ALARM
I
Read Input Register
(Function 04)
15149 0 3
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
REG_ALARM_EXTRA_CONTROLLER_
CLEAR_ALARM
I
Holding Register
(Function 03/06/16)
15150 0 1
Signal to clear the alarm
REG_ALARM_EXTERNAL_STOP_ALARM I
Read Input Register
(Function 04)
15156 0 3
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
REG_ALARM_EXTERNAL_STOP_CLEAR_
ALARM
I
Holding Register
(Function 03/06/16)
15157 0 1
Signal to clear the alarm
REG_ALARM_RH_ALARM I
Read Input Register
(Function 04)
15163 0 3
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
REG_ALARM_RH_CLEAR_ALARM I
Holding Register
(Function 03/06/16)
15164 0 1
Signal to clear the alarm
REG_ALARM_CO2_ALARM I
Read Input Register
(Function 04)
15170 0 3
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
REG_ALARM_CO2_CLEAR_ALARM I
Holding Register
(Function 03/06/16)
15171 0 1
Signal to clear the alarm
REG_ALARM_LOW_SAT_ALARM I
Read Input Register
(Function 04)
15177 0 3
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
REG_ALARM_LOW_SAT_CLEAR_ALARM I
Holding Register
(Function 03/06/16)
15178 0 1
Signal to clear the alarm
REG_ALARM_BYF_ALARM I
Read Input Register
(Function 04)
15184
Alarm active/inactive
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
REG_ALARM_BYF_CLEAR_ALARM I
Holding Register
(Function 03/06/16)
15185 0
Signal to clear the alarm
REG_ALARM_MANUAL_OVERRIDE_
OUTPUTS_ALARM
I
Read Input Register
(Function 04)
15502 0 3
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
REG_ALARM_MANUAL_OVERRIDE_
OUTPUTS_CLEAR_ALARM
I
Holding Register
(Function 03/06/16)
15503 0 1
Signal to clear the alarm
REG_ALARM_PDM_RHS_ALARM I
Read Input Register
(Function 04)
15509 0 3
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
REG_ALARM_PDM_RHS_CLEAR_ALARM I
Holding Register
(Function 03/06/16)
15510 0 1
Signal to clear the alarm
REG_ALARM_PDM_EAT_ALARM I
Read Input Register
(Function 04)
15516 0 3
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
REG_ALARM_PDM_EAT_CLEAR_ALARM I
Holding Register
(Function 03/06/16)
15517 0 1
Signal to clear the alarm
REG_ALARM_MANUAL_FAN_STOP_
ALARM
I
Read Input Register
(Function 04)
15523 0 3
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
| 2.1