SAVE MODBUS VARIABLE LIST 20210301 REV36

Modbus variable list |
3
Symbolic register name
Sig.
Modbus Reg. type Mod-
bus
Adr.
Min Max Description
REG_USERMODE_REFRESH_AIRFLOW_
LEVEL_SAF
I
Holding Register
(Function 03/06/16)
1137 3 5
Fan speed level for mode Refresh
3: Normal
4: High
5: Maximum
REG_USERMODE_REFRESH_AIRFLOW_
LEVEL_EAF
I
Holding Register
(Function 03/06/16)
1138 3 5
Fan speed level for mode Refresh
3: Normal
4: High
5: Maximum
REG_USERMODE_FIREPLACE_AIRFLOW_
LEVEL_SAF
I
Holding Register
(Function 03/06/16)
1139 3 5
Fan speed level for mode Fire Place
3: Normal
4: High
5: Maximum
REG_USERMODE_FIREPLACE_AIRFLOW_
LEVEL_EAF
I
Holding Register
(Function 03/06/16)
1140 1 3
Fan speed level for mode Fire Place
1: Minimum
2: Low
3: Normal
REG_USERMODE_AWAY_AIRFLOW_
LEVEL_SAF
I
Holding Register
(Function 03/06/16)
1141 0 3
Fan speed level for mode Away.
0: Off(1)
1: Minimum
2: Low
3: Normal.
(1): value Off only allowed if contents of
register REG_FAN_MANUAL_STOP_
ALLOWED is 1.
REG_USERMODE_AWAY_AIRFLOW_
LEVEL_EAF
I
Holding Register
(Function 03/06/16)
1142 0 3
Fan speed level for mode Away.
0: Off(1)
1: Minimum
2: Low
3: Normal.
(1): value Off only allowed if contents of
register REG_FAN_MANUAL_STOP_
ALLOWED is 1.
REG_USERMODE_HOLIDAY_AIRFLOW_
LEVEL_SAF
I
Holding Register
(Function 03/06/16)
1143 0 3
Fan speed level for mode Holiday.
0: Off(1)
1: Minimum
2: Low
3: Normal.
(1): value Off only allowed if contents of
register REG_FAN_MANUAL_STOP_
ALLOWED is 1.
REG_USERMODE_HOLIDAY_AIRFLOW_
LEVEL_EAF
I
Holding Register
(Function 03/06/16)
1144 0 3
Fan speed level for mode Holiday.
0: Off(1)
1: Minimum
2: Low
3: Normal.
(1): value Off only allowed if contents of
register REG_FAN_MANUAL_STOP_
ALLOWED is 1.
REG_USERMODE_COOKERHOOD_
AIRFLOW_LEVEL_SAF
I
Holding Register
(Function 03/06/16)
1145 1 5
Fan speed level for mode Cooker Hood
2: Low
3: Normal
4: High
REG_USERMODE_COOKERHOOD_
AIRFLOW_LEVEL_EAF
I
Holding Register
(Function 03/06/16)
1146 1 5
Fan speed level for mode Cooker Hood
1: Minimum
2: Low
3: Normal
REG_USERMODE_VACUUMCLEANER_
AIRFLOW_LEVEL_SAF
I
Holding Register
(Function 03/06/16)
1147 1 5
Fan speed level for mode Vacuum Cleaner
2: Low
3: Normal
4: High
REG_USERMODE_VACUUMCLEANER_
AIRFLOW_LEVEL_EAF
I
Holding Register
(Function 03/06/16)
1148 1 5
Fan speed level for mode Vacuum Cleaner
1: Minimum
2: Low
3: Normal
REG_USERMODE_CROWDED_T_OFFSET
I*
Holding Register
(Function 03/06/16)
1151 -100 0
Temperature setpoint offset for user mode
Crowded
| 2.1