SAVE VTR 300B SERVICE AND ACCESSORIES INSTALLATIONV1 20210616 121938589

Accessories
|
35
5.3.2 Internal water heater
A water heating battery can be installed inside the unit and connected to water system.
WH water heating battery
FPT frost protection sensor
SAT supply air temperature sensor
S actuator for valve
1 Outdoor air
2 Supply air
3 Extract air
4 Exhaust air
Component/product Article number:
Water coil SAVE VTR 300 141700
RVAZ4 24A Actuator 0-10V (S) 9862
ZTV 15-0,4 2-way valve 9829
ZTV 15-0,6 2-way valve 6571
ZTR 15-0,4 valve 3-way 9670
ZTR 15-0,6 valve 3-way 6573
Transformer 24V 202692
Installation and connection
1. Remove plug and add the frost protection sensor. Tread seal the sensor.
2. Install water heater in the unit. Connect pipes, 2/3–way valve and actuator.
Important
Do NOT use 24V DC power output from the connection board for valve actuator.
3. Connect actuator (S) to any free analog output.
Fig. 10 Water heater connections
Configuration
1. Go to Service menu
2. Enter password (default 1111)
| v01