SAVE MODBUS VARIABLE LIST 20210301 REV36
Table Of Contents
- 1 Information
- 2 Modbus variable list
- 2.1 Demand Control
- 2.2 User modes
- 2.3 Airflow Control
- 2.4 Outdoor Airflow Compensation
- 2.5 Temperature Control
- 2.6 Cooler
- 2.7 Heater
- 2.8 Extra Controller
- 2.9 Change-over (Heating/Cooling)
- 2.10 Moisture transfer control
- 2.11 Cooling recovery
- 2.12 ECO mode
- 2.13 Free Cooling
- 2.14 Week Schedule
- 2.15 Time and Date
- 2.16 Filter replacement
- 2.17 Analog Input values (Temperatures, CO2, RH)
- 2.18 Digital Input functions
- 2.19 Output values
- 2.20 Alarms
- 2.21 System settings
- 2.22 Modbus
- 2.23 Unit Backups
- 3 Revision table
Modbus variable list |
3
Symbolic register name
Sig.
Modbus Reg. type Mod-
bus
Adr.
Min Max Description
REG_USERMODE_REFRESH_AIRFLOW_
LEVEL_SAF
I
Holding Register
(Function 03/06/16)
1137 3 5
Fan speed level for mode Refresh
3: Normal
4: High
5: Maximum
REG_USERMODE_REFRESH_AIRFLOW_
LEVEL_EAF
I
Holding Register
(Function 03/06/16)
1138 3 5
Fan speed level for mode Refresh
3: Normal
4: High
5: Maximum
REG_USERMODE_FIREPLACE_AIRFLOW_
LEVEL_SAF
I
Holding Register
(Function 03/06/16)
1139 3 5
Fan speed level for mode Fire Place
3: Normal
4: High
5: Maximum
REG_USERMODE_FIREPLACE_AIRFLOW_
LEVEL_EAF
I
Holding Register
(Function 03/06/16)
1140 1 3
Fan speed level for mode Fire Place
1: Minimum
2: Low
3: Normal
REG_USERMODE_AWAY_AIRFLOW_
LEVEL_SAF
I
Holding Register
(Function 03/06/16)
1141 0 3
Fan speed level for mode Away.
0: Off(1)
1: Minimum
2: Low
3: Normal.
(1): value Off only allowed if contents of
register REG_FAN_MANUAL_STOP_
ALLOWED is 1.
REG_USERMODE_AWAY_AIRFLOW_
LEVEL_EAF
I
Holding Register
(Function 03/06/16)
1142 0 3
Fan speed level for mode Away.
0: Off(1)
1: Minimum
2: Low
3: Normal.
(1): value Off only allowed if contents of
register REG_FAN_MANUAL_STOP_
ALLOWED is 1.
REG_USERMODE_HOLIDAY_AIRFLOW_
LEVEL_SAF
I
Holding Register
(Function 03/06/16)
1143 0 3
Fan speed level for mode Holiday.
0: Off(1)
1: Minimum
2: Low
3: Normal.
(1): value Off only allowed if contents of
register REG_FAN_MANUAL_STOP_
ALLOWED is 1.
REG_USERMODE_HOLIDAY_AIRFLOW_
LEVEL_EAF
I
Holding Register
(Function 03/06/16)
1144 0 3
Fan speed level for mode Holiday.
0: Off(1)
1: Minimum
2: Low
3: Normal.
(1): value Off only allowed if contents of
register REG_FAN_MANUAL_STOP_
ALLOWED is 1.
REG_USERMODE_COOKERHOOD_
AIRFLOW_LEVEL_SAF
I
Holding Register
(Function 03/06/16)
1145 1 5
Fan speed level for mode Cooker Hood
2: Low
3: Normal
4: High
REG_USERMODE_COOKERHOOD_
AIRFLOW_LEVEL_EAF
I
Holding Register
(Function 03/06/16)
1146 1 5
Fan speed level for mode Cooker Hood
1: Minimum
2: Low
3: Normal
REG_USERMODE_VACUUMCLEANER_
AIRFLOW_LEVEL_SAF
I
Holding Register
(Function 03/06/16)
1147 1 5
Fan speed level for mode Vacuum Cleaner
2: Low
3: Normal
4: High
REG_USERMODE_VACUUMCLEANER_
AIRFLOW_LEVEL_EAF
I
Holding Register
(Function 03/06/16)
1148 1 5
Fan speed level for mode Vacuum Cleaner
1: Minimum
2: Low
3: Normal
REG_USERMODE_CROWDED_T_OFFSET
I*
Holding Register
(Function 03/06/16)
1151 -100 0
Temperature setpoint offset for user mode
Crowded
| 2.1