Modbus variable list |
5
Symbolic register name
Sig.
Modbus Reg. type Mod-
bus
Adr.
Min Max Description
REG_PRESSURE_GUARD_AIRFLOW_
LEVEL_SAF
I
Holding Register
(Function 03/06/16)
1177 0 5
Fan speed level for configurable pressure
guard function.
0: Off
1: Minimum
2: Low
3: Normal
4: High
5: Maximum
REG_PRESSURE_GUARD_AIRFLOW_
LEVEL_EAF
I
Holding Register
(Function 03/06/16)
1178 0 5
Fan speed level for configurable pressure
guard function.
0: Off
1: Minimum
2: Low
3: Normal
4: High
5: Maximum
REG_SENSOR_DI_AWAY I
Read Input Register
(Function 04)
12301 0 1
Value of physical Digital Input of Away
function
REG_SENSOR_DI_HOLIDAY I
Read Input Register
(Function 04)
12302 0 1
Value of physical Digital Input of Holiday
function
REG_SENSOR_DI_FIREPLACE I
Read Input Register
(Function 04)
12303 0 1
Value of physical Digital Input of Fireplace
function
REG_SENSOR_DI_REHRESH I
Read Input Register
(Function 04)
12304 0 1
Value of physical Digital Input of Refresh
function
REG_SENSOR_DI_CROWDED I
Read Input Register
(Function 04)
12305 0 1
Value of physical Digital Input of Crowded
function
REG_SENSOR_DI_COOKERHOOD I
Read Input Register
(Function 04)
12306 0 1
Value of physical Digital Input of
Cookerhood function
REG_SENSOR_DI_VACUUMCLEANER I
Read Input Register
(Function 04)
12307 0 1
Value of physical Digital Input of Vacuum
Cleaner function
REG_USERMODE_HOLIDAY_DI_OFF_
DELAY
I
Holding Register
(Function 03/06/16)
1181 0 365
Off delay for DI
REG_USERMODE_AWAY_DI_OFF_DELAY I
Holding Register
(Function 03/06/16)
1182 0 72
Off delay for DI
REG_USERMODE_FIRPLACE_DI_OFF_
DELAY
I
Holding Register
(Function 03/06/16)
1183 0 60
Off delay for DI
REG_USERMODE_REFRESH_DI_OFF_
DELAY
I
Holding Register
(Function 03/06/16)
1184 0 240
Off delay for DI
REG_USERMODE_CROWDED_DI_OFF_
DELAY
I
Holding Register
(Function 03/06/16)
1185 0 8
Off delay for DI
REG_CDI1_OFF_DELAY I
Holding Register
(Function 03/06/16)
1188 0 240
Off delay for DI
REG_CDI2_OFF_DELAY I
Holding Register
(Function 03/06/16)
1189 0 240
Off delay for DI
REG_CDI3_OFF_DELAY I
Holding Register
(Function 03/06/16)
1190 0 240
Off delay for DI
REG_SPEED_CDI1_SAF I
Read Input Register
(Function 04)
1221
SAF speed value for user mode Holiday.(1):
Depends on regulation type. Value can be
%, RPM, Pressure or Flow
REG_SPEED_CDI1_EAF I
Read Input Register
(Function 04)
1222
EAF speed value for user mode Holiday.(1):
Depends on regulation type. Value can be
%, RPM, Pressure or Flow
REG_SPEED_CDI2_SAF I
Read Input Register
(Function 04)
1223
SAF speed value for mode Cooker Hood.(1):
Depends on regulation type. Value can be
%, RPM, Pressure or Flow
REG_SPEED_CDI2_EAF I
Read Input Register
(Function 04)
1224
EAF speed value for mode Cooker Hood.(1):
Depends on regulation type. Value can be
%, RPM, Pressure or Flow
REG_SPEED_CDI3_SAF I
Read Input Register
(Function 04)
1225
SAF speed value for mode Vacuum Cleaner.
(1): Depends on regulation type. Value can
be %, RPM, Pressure or Flow
REG_SPEED_CDI3_EAF I
Read Input Register
(Function 04)
1226
EAF speed value for mode Vacuum Cleaner.
(1): Depends on regulation type. Value can
be %, RPM, Pressure or Flow
| 2.1