SAVE MODBUS VARIABLE LIST 20210301 REV36
Table Of Contents
- 1 Information
- 2 Modbus variable list
- 2.1 Demand Control
- 2.2 User modes
- 2.3 Airflow Control
- 2.4 Outdoor Airflow Compensation
- 2.5 Temperature Control
- 2.6 Cooler
- 2.7 Heater
- 2.8 Extra Controller
- 2.9 Change-over (Heating/Cooling)
- 2.10 Moisture transfer control
- 2.11 Cooling recovery
- 2.12 ECO mode
- 2.13 Free Cooling
- 2.14 Week Schedule
- 2.15 Time and Date
- 2.16 Filter replacement
- 2.17 Analog Input values (Temperatures, CO2, RH)
- 2.18 Digital Input functions
- 2.19 Output values
- 2.20 Alarms
- 2.21 System settings
- 2.22 Modbus
- 2.23 Unit Backups
- 3 Revision table
Modbus variable list |
17
2.17 Analog Input values (Temperatures, CO2, RH)
Symbolic register name
Sig.
Modbus Reg. type Mod-
bus
Adr.
Min Max Description
REG_SENSOR_FPT
I*
Holding Register
(Function 03/06/16)
12101 -400 800
Frost Protection Temperature sensor value
(Water Heater)
REG_SENSOR_OAT
I*
Holding Register
(Function 03/06/16)
12102 -400 800
Outdoor Air Temperature sensor (standard)
REG_SENSOR_SAT
I*
Holding Register
(Function 03/06/16)
12103 -400 800
Supply Air Temperature sensor (standard)
REG_SENSOR_RAT
I*
Holding Register
(Function 03/06/16)
12104 -400 800
Room Air Temperature sensor (accessory)
REG_SENSOR_EAT
I*
Holding Register
(Function 03/06/16)
12105 -400 800
Extract Air Temperature sensor (accessory)
REG_SENSOR_ECT
I*
Holding Register
(Function 03/06/16)
12106 -400 800
Extra Controller Temperature sensor
(accessory)
REG_SENSOR_EFT
I*
Holding Register
(Function 03/06/16)
12107 -400 800
Efficiency temperature sensor (accessory)
REG_SENSOR_OHT
I*
Holding Register
(Function 03/06/16)
12108 -400 800
Over Heat Temperature sensor (Electrical
Heater)
REG_SENSOR_RHS I
Holding Register
(Function 03/06/16)
12109 0 100
Relative Humidity Sensor (Accessory)
REG_SENSOR_CO2S I
Holding Register
(Function 03/06/16)
12115 0 2000
CO2 value (accessory)
REG_SENSOR_PDM_EAT_VALUE I
Holding Register
(Function 03/06/16)
12544 -400 800
PDM EAT sensor value (standard)
REG_SENSOR_RHS_PDM I
Holding Register
(Function 03/06/16)
12136 0 100
PDM RHS sensor value (standard)
REG_SENSOR_CO2S_1 I
Holding Register
(Function 03/06/16)
12151 0 2000
CO2 sensor value - UI1 (accessory)
REG_SENSOR_CO2S_2 I
Holding Register
(Function 03/06/16)
12152 0 2000
CO2 sensor value - UI2 (accessory)
REG_SENSOR_CO2S_3 I
Holding Register
(Function 03/06/16)
12153 0 2000
CO2 sensor value - UI3 (accessory)
REG_SENSOR_CO2S_4 I
Holding Register
(Function 03/06/16)
12154 0 2000
CO2 sensor value - UI4 (accessory)
REG_SENSOR_CO2S_5 I
Holding Register
(Function 03/06/16)
12155 0 2000
CO2 sensor value - UI5 (accessory)
REG_SENSOR_CO2S_6 I
Read Input Register
(Function 04)
12156
CO2 sensor value - UI6 (accessory)
REG_SENSOR_RHS_1 I
Holding Register
(Function 03/06/16)
12161 0 100
RH sensor value - UI1 (accessory)
REG_SENSOR_RHS_2 I
Holding Register
(Function 03/06/16)
12162 0 100
RH sensor value - UI2 (accessory)
REG_SENSOR_RHS_3 I
Holding Register
(Function 03/06/16)
12163 0 100
RH sensor value - UI3 (accessory)
REG_SENSOR_RHS_4 I
Holding Register
(Function 03/06/16)
12164 0 100
RH sensor value - UI4 (accessory)
REG_SENSOR_RHS_5 I
Holding Register
(Function 03/06/16)
12165 0 100
RH sensor value - UI5 (accessory)
REG_SENSOR_RHS_6 I
Read Input Register
(Function 04)
12166 0 100
RH sensor value - UI6 (accessory)
REG_INPUT_ANALOG_UI_1 I
Holding Register
(Function 03/06/16)
12011 mV
REG_INPUT_ANALOG_UI_2 I
Holding Register
(Function 03/06/16)
12012 mV
REG_INPUT_ANALOG_UI_3 I
Holding Register
(Function 03/06/16)
12013 mV
REG_INPUT_ANALOG_UI_4 I
Holding Register
(Function 03/06/16)
12014 mV
REG_INPUT_ANALOG_UI_5 I
Holding Register
(Function 03/06/16)
12015 mV