SAVE VTR 700 SERVICE AND ACCESSORIES INSTALLATIONV1 20210507 104848956

Configuration |
17
Range: 0–10 V / 2–10 V / 10–0 V / 10–2 V.
Heater
Choose heater type. Each selection unlocks additional configuration options. Default setting is based on unit type.
Available types: None / Electrical / Water / Change-over.
Set actuator type. Default value is 0–10 V.
Range: 0–10 V / 2–10 V / 10–0 V / 10–2 V.
Set circulation pump temperature. Default setting is 10°C. This option is available if Water / Change-over heater
type is selected.
Range: 0–20°C.
Set circulation pump stop delay. Default setting is 5 minutes. This option is available if Water / Change-over heat-
er type is selected.
Range: Off / 1–60 min.
Cooler
Choose cooler type. Each selection unlocks additional configuration options. Default setting is None.
Available types: None / Water / Change-over.
Set outdoor air temperature interlock. Default setting is 10°C.
Range: 0–20°C.
Set actuator type. Default value is 0–10 V
Range: 0–10 V / 2–10 V / 10–0 V / 10–2 V.
Set circulation pump stop delay. Default setting is 5 minutes. This option is available if Water / Change-over heat-
er type is selected.
Range: Off / 1–60 min.
Extra Controller
Choose extra controller type. Each selection unlocks additional configuration options. Default setting is None.
Available types: None / Preheater / Heating / Cooling / GEO Exchanger.
Set temperature set point of the extra controller. Default value is 0°C.
Range: –30°C 40°C.
Set P-band. Default setting is 4°C.
Range: 1-60°C.
Set I-time. Default setting is Off.
Range: Off / 1–240 sec.
Set actuator type. Default value is 0–10 V.
Range: 0–10 V / 2–10 V / 10–0 V / 10–2 V.
Set circulation pump temperature. Default setting is 0°C. This option is available if Preheater controller type is
selected.
Range: 0–20°C.
Set circulation pump stop delay. Default setting is 5 minutes.
Range: Off / 1–60 min.
Bellow menus are available if controller type is selected as GEO Exchanger.
Pre-heater settings:
Set-point (-30 °C to + 10 °C).
Activation temperature (-30 °C to 0 °C).
Pre-cooler settings:
Set-point (10 °C to 30 °C).
Activation temperature (15 °C to 30 °C).
| v01