SAVE VTR 700 SERVICE AND ACCESSORIES INSTALLATIONV1 20210507 104848956

32
|
Accessories
ELH Electrical heater
OHT overheat protection sensor
1 Outdoor air
2 Supply air
3 Extract air
4 Exhaust air
Component/product Article number:
El. Reheater VTR 700 R 1,67kW (for right version model) 141100
El. Reheater VTR 700 L 1,67kW (for left version model) 138100
Installation and connection
1 Remove cover plates from electrical connections (pos.
1) and heater (pos. 2) compartments by removing 4
screws from each plate at the front.
2 Remove knobs (pos. 2) that will hold reheater in
place. Insert electrical reheater (pos. 1) into dedicated
compartment, secure reheater with previously re-
moved knobs (pos. 2).
Lead reheater control, TRIAC and overheat protection
sensor wires through separate holes in the panel (pos.
3) to electrical connections compartment.
3
Connect reheater control wires to the terminal
block marked as HEATER (pos. 4) on the main cir-
cuit board. Connect blue wire to N socket, brown
wire to L socket.
Connect TRIAC wires to the terminal block marked
as TRIAC (pos. 5) on the main circuit board. Connect
black wire to G socket, brown wire to A1 socket,
gray wire to A2 socket.
Connect overheat protection sensor to any free
analog input on the main circuit board (pos. 6).
Connect black wire to ground (GND), red fire to
analog input.
4 Place back covers of reheater and the main circuit
board and secure them with screws.
| v01