SAVE MODBUS VARIABLE LIST 20210301 REV36

20
| Modbus variable list
Symbolic register name
Sig.
Modbus Reg. type Mod-
bus
Adr.
Min Max Description
REG_ALARM_SAF_CTRL_ALARM I
Read Input Register
(Function 04)
15002 0 3
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
REG_ALARM_SAF_CTRL_CLEAR_ALARM I
Holding Register
(Function 03/06/16)
15003 0 1
Signal to clear the alarm
REG_ALARM_EAF_CTRL_ALARM I
Read Input Register
(Function 04)
15009 0 3
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
REG_ALARM_EAF_CTRL_CLEAR_ALARM I
Holding Register
(Function 03/06/16)
15010 0 1
Signal to clear the alarm
REG_ALARM_FROST_PROT_ALARM I
Read Input Register
(Function 04)
15016 0 3
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
REG_ALARM_FROST_PROT_CLEAR_
ALARM
I
Holding Register
(Function 03/06/16)
15017 0 1
Signal to clear the alarm
REG_ALARM_DEFROSTING_ALARM I
Read Input Register
(Function 04)
15023 0 3
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
REG_ALARM_DEFROSTING_CLEAR_
ALARM
I
Holding Register
(Function 03/06/16)
15024 0 1
Signal to clear the alarm
REG_ALARM_SAF_RPM_ALARM I
Read Input Register
(Function 04)
15030 0 3
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
REG_ALARM_SAF_RPM_CLEAR_ALARM I
Holding Register
(Function 03/06/16)
15031 0 1
Signal to clear the alarm
REG_ALARM_EAF_RPM_ALARM I
Read Input Register
(Function 04)
15037 0 3
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
REG_ALARM_EAF_RPM_CLEAR_ALARM I
Holding Register
(Function 03/06/16)
15038 0 1
Signal to clear the alarm
REG_ALARM_FPT_ALARM I
Read Input Register
(Function 04)
15058 0 3
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
REG_ALARM_FPT_CLEAR_ALARM I
Holding Register
(Function 03/06/16)
15059 0 1
Signal to clear the alarm
REG_ALARM_OAT_ALARM I
Read Input Register
(Function 04)
15065 0 3
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
REG_ALARM_OAT_CLEAR_ALARM I
Holding Register
(Function 03/06/16)
15066 0 1
Signal to clear the alarm
REG_ALARM_SAT_ALARM I
Read Input Register
(Function 04)
15072 0 3
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
REG_ALARM_SAT_CLEAR_ALARM I
Holding Register
(Function 03/06/16)
15073 0 1
Signal to clear the alarm
REG_ALARM_RAT_ALARM I
Read Input Register
(Function 04)
15079 0 3
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
| 2.1