Modbus variable list |
21
Symbolic register name
Sig.
Modbus Reg. type Mod-
bus
Adr.
Min Max Description
REG_ALARM_RAT_CLEAR_ALARM I
Holding Register
(Function 03/06/16)
15080 0 1
Signal to clear the alarm
REG_ALARM_EAT_ALARM I
Read Input Register
(Function 04)
15086 0 3
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
REG_ALARM_EAT_CLEAR_ALARM I
Holding Register
(Function 03/06/16)
15087 0 1
Signal to clear the alarm
REG_ALARM_ECT_ALARM I
Read Input Register
(Function 04)
15093 0 3
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
REG_ALARM_ECT_CLEAR_ALARM I
Holding Register
(Function 03/06/16)
15094 0 1
Signal to clear the alarm
REG_ALARM_EFT_ALARM I
Read Input Register
(Function 04)
15100 0 3
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
REG_ALARM_EFT_CLEAR_ALARM I
Holding Register
(Function 03/06/16)
15101 0 1
Signal to clear the alarm
REG_ALARM_OHT_ALARM I
Read Input Register
(Function 04)
15107 0 3
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
REG_ALARM_OHT_CLEAR_ALARM I
Holding Register
(Function 03/06/16)
15108 0 1
Signal to clear the alarm
REG_ALARM_EMT_ALARM I
Read Input Register
(Function 04)
15114 0 3
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
REG_ALARM_EMT_CLEAR_ALARM I
Holding Register
(Function 03/06/16)
15115 0 1
Signal to clear the alarm
REG_ALARM_RGS_ALARM I
Read Input Register
(Function 04)
15121 0 3
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
REG_ALARM_RGS_CLEAR_ALARM I
Holding Register
(Function 03/06/16)
15122 0 1
Signal to clear the alarm
REG_ALARM_BYS_ALARM I
Read Input Register
(Function 04)
15128 0 3
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
REG_ALARM_BYS_CLEAR_ALARM I
Holding Register
(Function 03/06/16)
15129 0 1
Signal to clear the alarm
REG_ALARM_SECONDARY_AIR_ALARM I
Read Input Register
(Function 04)
15135 0 3
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
REG_ALARM_SECONDARY_AIR_CLEAR_
ALARM
I
Holding Register
(Function 03/06/16)
15136 0 1
Signal to clear the alarm
REG_ALARM_FILTER_ALARM I
Read Input Register
(Function 04)
15142 0 3
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
REG_ALARM_FILTER_CLEAR_ALARM I
Holding Register
(Function 03/06/16)
15143 0 1
Signal to clear the alarm
| 2.1