SAVE MODBUS VARIABLE LIST 20210301 REV36

4
| Modbus variable list
Symbolic register name
Sig.
Modbus Reg. type Mod-
bus
Adr.
Min Max Description
REG_USERMODE_MODE I
Read Input Register
(Function 04)
1161 0 12
Active User mode.
0: Auto
1: Manual
2: Crowded
3: Refresh
4: Fireplace
5: Away
6: Holiday
7: Cooker Hood
8: Vacuum Cleaner
9: CDI1
10: CDI2
11: CDI3
12: PressureGuard
REG_USERMODE_HMI_CHANGE_
REQUEST
I
Holding Register
(Function 03/06/16)
1162 0 7
New desired user mode as requested by
HMI
0: None
1: AUTO
2: Manual
3: Crowded
4: Refresh
5: Fireplace
6: Away
7: Holiday
REG_CDI_1_AIRFLOW_LEVEL_SAF I
Holding Register
(Function 03/06/16)
1171 0 5
Fan speed level for configurable digital input
1.
0: Off
1: Minimum
2: Low
3: Normal
4: High
5: Maximum
REG_CDI_1_AIRFLOW_LEVEL_EAF I
Holding Register
(Function 03/06/16)
1172 0 5
Fan speed level for configurable digital input
1.
0: Off
1: Minimum
2: Low
3: Normal
4: High
5: Maximum
REG_CDI_2_AIRFLOW_LEVEL_SAF I
Holding Register
(Function 03/06/16)
1173 0 5
Fan speed level for configurable digital input
2.
0: Off
1: Minimum
2: Low
3: Normal
4: High
5: Maximum
REG_CDI_2_AIRFLOW_LEVEL_EAF I
Holding Register
(Function 03/06/16)
1174 0 5
Fan speed level for configurable digital input
2.
0: Off
1: Minimum
2: Low
3: Normal
4: High
5: Maximum
REG_CDI_3_AIRFLOW_LEVEL_SAF I
Holding Register
(Function 03/06/16)
1175 0 5
Fan speed level for configurable digital input
3.
0: Off
1: Minimum
2: Low
3: Normal
4: High
5: Maximum
REG_CDI_3_AIRFLOW_LEVEL_EAF I
Holding Register
(Function 03/06/16)
1176 0 5
Fan speed level for configurable digital input
3.
0: Off
1: Minimum
2: Low
3: Normal
4: High
5: Maximum
| 2.1