2.19 Output values
Symbolic register name
Sig.
Modbus Reg. type Mod-
bus
Adr.
Min
Max
Description
REG_SENSOR_RGS I
Read Input Register
(Function 04)
12112 0 1
Rotating guard Sensor input
REG_DO1_AFTER_MUX I
Read Input Register
(Function 04)
13301 0 1
Digital output after multiplexer
REG_DO2_AFTER_MUX I
Read Input Register
(Function 04)
13302 0 1
Digital output after multiplexer
REG_DO3_AFTER_MUX I
Read Input Register
(Function 04)
13303 0 1
Digital output after multiplexer
REG_DO4_AFTER_MUX I
Read Input Register
(Function 04)
13304 0 1
Digital output after multiplexer
REG_AO1_AFTER_MUX I
Read Input Register
(Function 04)
13311 0 100
Analog output after multiplexer
REG_AO2_AFTER_MUX I
Read Input Register
(Function 04)
13312 0 100
Analog output after multiplexer
REG_AO3_AFTER_MUX I
Read Input Register
(Function 04)
13313 0 100
Analog output after multiplexer
REG_AO4_AFTER_MUX I
Read Input Register
(Function 04)
13314 0 100
Analog output after multiplexer
REG_AO5_AFTER_MUX I
Read Input Register
(Function 04)
13315 0 100
Analog output after multiplexer
REG_OUTPUT_OUTDOOR_EXTRACT_
DAMPER
I
Read Input Register
(Function 04)
14004 0 1
Indicates if Outdoor/Exhaust air damper
signal is On/Off
REG_OUTPUT_Y2_ANALOG I
Read Input Register
(Function 04)
14103 0 100
Heat Exchanger AO state.
REG_OUTPUT_Y2_DIGITAL I
Read Input Register
(Function 04)
14104 0 1
Heat Exchanger DO state.0: Output not
active1: Output active
REG_OUTPUT_AO1 I
Read Input Register
(Function 04)
14351
Voltage signal from AO1
REG_OUTPUT_AO2 I
Read Input Register
(Function 04)
14352
Voltage signal from AO2
REG_OUTPUT_AO3 I
Read Input Register
(Function 04)
14353
Voltage signal from AO3
REG_OUTPUT_AO4 I
Read Input Register
(Function 04)
14354
Voltage signal from AO4
REG_OUTPUT_AO5 I
Read Input Register
(Function 04)
14355
Voltage signal from AO5
REG_OUTPUT_DO1 I
Read Input Register
(Function 04)
14361 0 1
State of DO1
REG_OUTPUT_DO2 I
Read Input Register
(Function 04)
14362 0 1
State of DO2
REG_OUTPUT_DO3 I
Read Input Register
(Function 04)
14363 0 1
State of DO3
REG_OUTPUT_DO4 I
Read Input Register
(Function 04)
14364 0 1
State of DO4
2.20 Alarms
Symbolic register name
Sig.
Modbus Reg. type Mod-
bus
Adr.
Min Max Description
REG_FILTER_ALARM_WAS_DETECTED I
Read Input Register
(Function 04)
7007
Indicates if the filter warning alarm was
generated.
REG_OUTPUT_ALARM I
Read Input Register
(Function 04)
14003 0 1
Sum Alarm DO
0: Output not active
1: Output active