SAVE VTC 500 USER MANUALV01 20210316

10
|
Maintenance
Use Allen key (not included) to unlock locks at the top and bottom of the front cover. Open the front cover. Remove
two screws at the top and bottom of the side cover to open it.
4.3 To change filters
The filters cannot be cleaned and must be changed as necessary. This is normally done 1–2 times per year depending
on the air pollution at the installation site.
It is very important to change filters regularly for performance and energy efficiency of the unit.
Each filter has a label with an part number for identification. Provide this number when ordering new filters.
When it’s time to change the filters an alarm is shown on
the control panel display. When this occurs do the
following:
1. Stop the unit by disconnecting the mains.
2. Open the front hatch. See chapter 4.2.
3. Remove old filters and insert new ones. Make sure fil-
ters are not mixed up during the replacement process.
Supply and extract air filters may be different.
4. Close and lock the front hatch and connect the unit to
mains.
5. Reset the filter time as described below (chapter
4.3.1). Depending on the condition of the filter, you
might need to change the operation time for the filter.
4.3.1 To reset the filter change time
Once filter is changed, it is necessary to reset filter time. Go to Filter menu
(see 3.2.2 Home screen overview, page 4, pos. E) or if filter alarm is present,
click on alarm status line (see 3.2.2 Home screen overview, page 4, pos. 5)
and select filter alarm. Select CHANGE FILTER, in the pop up menu define a
new filter period and press OK to confirm selection.
Filter time is now reset.
Note:
The menu is locked by default. Enter a password (default
password is 1111).
To reset filter change timer for SAVE LIGHT
Push and hold
and buttons for 3 seconds to reset the filter timer
(filter change LED will turn off).