Modbus variable list |
23
Symbolic register name
Sig.
Modbus Reg. type Mod-
bus
Adr.
Min Max Description
REG_ALARM_MANUAL_FAN_STOP_
CLEAR_ALARM
I
Holding Register
(Function 03/06/16)
15524 0 1
Signal to clear the alarm
REG_ALARM_OVERHEAT_
TEMPERATURE_ALARM
I
Read Input Register
(Function 04)
15530 0 3
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
REG_ALARM_OVERHEAT_
TEMPERATURE_CLEAR_ALARM
I
Holding Register
(Function 03/06/16)
15531 0 1
Signal to clear the alarm
REG_ALARM_FIRE_ALARM_ALARM I
Read Input Register
(Function 04)
15537 0 3
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
REG_ALARM_FIRE_ALARM_CLEAR_
ALARM
I
Holding Register
(Function 03/06/16)
15538 0 1
Signal to clear the alarm
REG_ALARM_FILTER_WARNING_ALARM I
Read Input Register
(Function 04)
15544 0 3
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
REG_ALARM_FILTER_WARNING_CLEAR_
ALARM
I
Holding Register
(Function 03/06/16)
15545 0 1
Signal to clear the alarm
REG_ALARM_FILTER_WARNING_
ALARM_ERROR_DURATION_COUNTER
I
Read Input Register
(Function 04)
15549
Counter for delay
REG_ALARM_TYPE_A I
Read Input Register
(Function 04)
15901 0 1
Indicates if an alarm Type A is active
REG_ALARM_TYPE_B I
Read Input Register
(Function 04)
15902 0 1
Indicates if an alarm Type B is active
REG_ALARM_TYPE_C I
Read Input Register
(Function 04)
15903 0 1
Indicates if an alarm Type C is active
2.21 System settings
Symbolic register name
Sig.
Modbus Reg. type Mod-
bus
Adr.
Min Max Description
REG_PASSWD_ADMIN I
Holding Register
(Function 03/06/16)
16001
Administrator password.
Bit 12-15: digit 1
Bit 8-11: digit 2
Bit 4-7: digit 3
Bit 0-3: digit 4
REG_LOCKED_USER I
Holding Register
(Function 03/06/16)
16002 0 1
Indicates if the User level is locked.
0: User menu locked
1: User menu not locked
REG_LOCKED_FILTER I
Holding Register
(Function 03/06/16)
16003 0 1
Indicates if the Filter menu is locked.
0: menu locked
1: menu not locked
REG_LOCKED_WEEK_SCHEDULE I
Holding Register
(Function 03/06/16)
16004 0 1
Indicates if the Week schedule menu is
locked.
0: menu locked
1: menu not locked
REG_PASSWD_USER_LEVEL_REQUIRED I
Holding Register
(Function 03/06/16)
16051 0 1
Home screen lock
REG_PASSWD_FILTER_REQUIRED I
Holding Register
(Function 03/06/16)
16052 0 1
Filter Change menu lock
REG_PASSWD_WEEK_SCHEDULE_
REQUIRED
I
Holding Register
(Function 03/06/16)
16053 0 1
Week schedule menu lock
REG_PASSWD_PC_SETTINGS I
Holding Register
(Function 03/06/16)
16061
REG_PASSWD_PC_UNLOCKED I
Read Input Register
(Function 04)
16062 0 1
REG_SUW_REQUIRED I
Holding Register
(Function 03/06/16)
16101 0 1
Indicates if the start-up wizard shall be
activated.
| 2.1