ZTV/ZTR
ZTV/ZTR
Externally threaded 2- and 3-way zone
valves
Valves used for control of hot and cold water in
climate, heating and ventilation systems. They can
also control glycol-mixed water in for example liquid
connected recovery systems. Intended to be used
together with the RVAZ4 actuators.
9 Size DN15…DN25
9 Kvs value 0.25…7.0
9 Media temperature 1…110°C
9 Pressure rating PN16
9 Rangeability better than 50:1
9 No leakage
Function
2-way valve
The valve is open when the stem is in its lowest position
and closed when the stem is in its upmost position.
2-way valve
3-way valve
The 3-way valve is closed between port A and port AB
(the ports opposite to one another) when the stem is in
its highest position. In this position, the valve is also open
between the bottom port B and the common supply port
AB. When the stem is in its lowest position, the 3-way
valve is completely open between port A and port AB and
consequently closed between the bottom port B and the
common port AB.
AB
A
B
3-way valve
No leakage in closed position
The valve has O-ring sealing between plug and seat, which
makes it completely tight in closed position. This makes
the valve very energy-efficient.