Operating instructions
Cleaning
The damper can be fully opened
for easy access to the inside of
the duct. Remember to write
down the setting for the damper
prior to opening. Set the
opening back to normal after
cleaning.
Loosen the screws for adjusting
the damper setting
.
Example
Formula given
qPk
i
Controlling the airflow
Size SPI 160
Pressure (measured) 30 Pa
K-factor (from label) 18
Entered in the equation:
6,983018
In this case the airflow is
98,6 l/s
Where
q = airflow (l/s)
k = K-factor
P
i
= tuning pressure
Tuning
Connect the hoses to the
measuring connections
and measure the
pressure.
Lock the setting by
tightening the screws after
tuning.