OP10 InstSV FR DE
INSTRUCTION
i
Read this instruction before installation
and wiring of the product
OPTIGO OP10
Consult documentation in all cases where this symbol
is used, in order to nd out the nature of the potential
hazards and any actions to be taken
1
OPTIGO S-OP10, S-OP10-230
Controller with display
Optigo OP10 is a pre-programmed, congurable controller. It has
10 inputs/outputs and can be congured to control temperature
(ventilation control with heating and cooling), water-heated radiator
heating with outdoor temperature dependent control-curve or
domestic hot water control.
From revision R20, it is possible to connect an external setpoint
device. The device can be used for control modes 1-4.
OP10 is available in two versions, OP10 with 24 V AC supply voltage
and OP10-230 with 230 V AC supply voltage.
All conguration and normal handling is done using the display and
the knob on the front.
Technical data
Supply voltage
OP10-230 230 V AC +10/-15%, 50/60 Hz
OP10 24 V AC ±15%, 50/60 Hz
Power consumption 6 VA
Ambient temperature 0...50°C (32...122°F)
Ambient humidity Max. 95% RH
Storage temperature -20...70°C (-4...158°F)
Display Numeric / graphic. Background illumination.
Inputs Refer to connection illustrations and table
below
Terminal blocks Disconnectable, so-called lift type for cable
cross-section 2.5 mm
2
Protection class IP20
Material, casing Polycarbonate, PC
Weight
OP10-230 370 g incl. terminals
OP10 215 g incl. terminals
Dimensions 122 x 120 x 64 mm (4,8 x 4,7 x 2,5 in)
(WxHxD incl. terminals)
Overvoltage category 3
Pollution degree 2
Setpoint values
Temperature Factory setting
Supply air 10...80°C (50...176°F) 21°C (70°F)
Cascade control, room 10...50°C (50...122°F) 21°C (70°F)
Radiator circuit control 10...40°C (50...104°F) 21°C (70°F)
(only when using
a room sensor)
External setpoint 0...40°C (32...104°F)
Domestic hot water 10…80°C (50...176°F) 55°C (131°F)
Neutral zone 0...10°C (32...50°F) 1°C (33,8°F)
P-band 0…99°C (32...210,2°F) 15°C (59°F)
I-time 0…990 s 60 s
D-factor 0…99 0
P-band cascade 0.5…99 15
Min. at cascade 0…99°C (32...201,2°F) 15 ºC (59°F)
Max. at cascade 0…99°C (32...201,2°F) 25 ºC (77°F)
Damper min. limit 0…99 (32...201,2°F) 10 ºC (50°F)
Start of outdoor compens. -30…50°C (-22...122°F) 10°C(50°F)
Outdoor compensation
at -20°C (-4°F) outdoor t. -10…10°C (14...50°F) 5°C(41°F)
Supply temperature
(water-heated radiator
heating)
at -20°C (-4°F) outdoor t. 0…99°C (32...210,2°F) 60°C (140°F)
at 20°C (68°F) outdoor t. 0…99°C (32...210,2°F) 20°C (68°F)
Frost protection 7°C (44.6°F), xed
SP. Shutdown mode 25°C (77°F), xed
Actuating time,
3-point actuator 10...300 s 120 s
Installation
OP10-230 must be installed in a casing (DIN-casing or similar) where
it can be used without risk of electric shock and where it fullls the
demands for the LVD-standard. See the section Installation in the
“Optigo OP10 Manual”.
Disconnection
The controller PO10-230 shall be connected to a switch or circuit
breaker in the building installation. This switch shall be in close prox-
imity to the controller and within easy reach of the operator, and shall
be marked as the disconnecting device for the equipment.
Overcurrent protection
The controller OP10-230 shall be protected by a fuse in the building
installation. The maximum load of the controller, 1000 VA, suggests a
6 A fuse.
Follow table 1 below for connection.
Table 1. I/O connection terminals
Terminal Designation Operation
1 G 24 V AC
Optigo 10 only
2 G0
3
8313K
JUL 13
EN
(0,003 sq.in)